    SIC-SING Connection

    Energy Sector

    Comparison of Alternatives

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Motivation for System Interconnections

    Improving Reliability, sharing of reserve capacity

    Possibility to use larger and more economical Power Plants

    Possibility to build power plants at favorable locations

    Utilization of most favorable energy source (e.g. Solar / Hydro)

    Power Exchange

    There are strong reasons to connect Transmission Networks

    Benefits

    Efforts

    interconnected Operation

    Advantages ofinterconnected Operation

    Advantages of

    Benefits,

    Efforts

    Size of interconnected Grid

    Benefits,

    Efforts

    Size of interconnected Grid

    OptimumOptimumOptimumOptimumOptimumOptimum

    Cost-to-Performance RatioCost-to-Performance Ratio

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Challenges System Interconnections

    Propagation of Disturbances, Blackout

    Synchronisation, frequency control

    Transmission Limits: Thermal, Voltage and Phase Angle

    Loop and Parallel Flows, Congestion Management

    Oscillations

    Load Shedding Strategies

    Fault Currents

    System Interconnection is a complex task and requires sound analisis

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Option 1: Short Connection (2 x 220 kV AC + HVDC BtB)

    Crucero

    Cardones

    Paposo

    Coloso/Esmeralda

    SING

    SIC

    Option 1: Short Connection 220 kV

    - 220 kV Line Paposo Col./Esm.

    - estimated 200 kms

    - Double Circuit

    - 400 MW

    - HVDC Back to Back in one extreme

    due to stability reasons

    assumed to be mandatory

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Option 2: Long Connection 500 kV AC Transmission Line

    Crucero

    Cardones

    Paposo

    Coloso/Esmeralda

    SING

    SIC

    Option 2a: Long Connection 500 kV

    -500 kV Line Cardones - Crucero

    -estimated 750 kms

    -Single Circuit

    -1000 MW

    -66% Series Compensation

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Option 2: Long Connection 500 kV AC Transmission Line

    Crucero

    Cardones

    Paposo

    Coloso/Esmeralda

    SING

    SIC

    Option 2a: Long Connection 500 kV

    -500 kV Line Cardones - Crucero

    -estimated 750 kms

    -Single Circuit

    -1000 MW

    -66% Series Compensation

    Option 2b: Long Connection 500 kV

    - Double Circuit,

    - 33% Series Compensation

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Option 2: Long Connection 500 kV AC Transmission Line 1000 MW

    Crucero

    Cardones

    Paposo

    Coloso/Esmeralda

    SING

    SIC

    Option 2a: Long Connection 500 kV

    -500 kV Line Cardones - Crucero

    -estimated 750 kms

    -Single Circuit

    -66% Series Compensation

    Option 2b: Long Connection 500 kV

    - Double Circuit,

    - 33% Series Compensation

    Option 2c: Long Connection 500 kV

    - Double Circuit

    - plus HVDC Back to Back in one extreme

    due to stability reasons

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Option 3: Long Connection 500 kV DC Transmission Line

    Crucero

    Cardones

    Paposo

    Coloso/Esmeralda

    SING

    SIC

    Option 3: Long Connection +/-500 kV

    - 500 kV DC Line Cardones - Crucero

    - estimated 750 kms

    - Bipole

    - 1000MW

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Technical Options

    Option 1

    2 x 220 kV AC

    + Back to Back

    max. 400MW

    Low Investment

    Stable only with

    BtB

    AC enables

    easy tapping

    High Losses

    Limited Capacity

    Additional

    Investment in

    existing system

    necesary

    Option 2a

    1 x 500 kV AC

    < 1000MW

    High Losses

    Limited Capacity

    Very High Risk

    no n-1 condition

    Known Solution

    AC enables

    easy tapping

    Low Investment

    Option 2b

    2 x 500 kV AC

    1000 MW

    High Risk

    Known Solution

    AC enables

    easy tapping

    Option 2c

    2 x 500 kV AC

    + Back to Back

    1000 MW

    Stable Solution

    AC enables

    easy tapping

    High Investment

    High Losses

    Option 3

    500 kV HVDC

    Bipole

    1000 MW

    Low Investment

    Low Losses

    High Power

    Stable Solution

    Limited tapping

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Options Estimated Total Cost

    Total Cost

    (est. Mio USD)

    700 1.350 1.000 1.350 900

    500 Mio USD

    1.000 Mio USD

    CAPEX (w/o reinforcment existing lines) CAPEX CAPEX CAPEX

    OPEX

    OPEX

    OPEX

    OPEX

    Mio USD, General Estimation

    w/o Basic Engineering

    OPEX Considers: Energy losses 80US$/MWH

    Power losses 1500USD/KW

    NPV 40 years, 7% rate

    CAPEX

    OPEX

    Option 1

    2 x 220 kV AC

    + Back to Back

    max. 400MW

    Option 2a

    1 x 500 kV AC

    < 1000MW

    Option 2b

    2 x 500 kV AC

    1000 MW

    Option 2c

    2 x 500 kV AC

    + Back to Back

    1000 MW

    Option 3

    500 kV HVDC

    Bipole

    1000 MW

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Estimated Break Even Distance 2 x 500 kV AC HVDC Bipole 1000 MW

    Break Even Distance Investment

    Kms

    0

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1000

    Break Even Total Cost

    0

    0

    100

    200

    300

    400

    500

    600

    700

    800

    900

    1.0

    00

    Kms

    AC

    DC

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Advantages HVDC Link

    -Stabilizing Function in case of failure in SING or SIC no cascading

    -DC Link can be rated according to real requirements, AC link must be

    overdimensioned due to stability reasons

    -Reconection possible independent of phase angle

    -No risk of subsynchronous oscillations

    -Controllability of Power Flow

    -Blackout Firewall

    -Mutual support between Systems in Emergency Situations

    HVDC is the proven, low risk Option to realize the SIC-SING Connection

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection How can HVDC help limiting Blackouts?

    From White Night to Black Night *Source: EURELECTRIC Task Force Final Report 06-2004

    Europe needs

    Enhancements, too

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection How can HVDC help limiting Blackouts?

    Existing

    Under Unstruction

    Planned

    HVDC EUROPE

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection How can HVDC help limiting Blackouts?

    The Interconnection

    CENTREL with UCPTE

    UCTE Synchronous Interconnections:

    Inter-Area Oscillations with Magnitudes up to

    1000 MW

    Damping Measures necessary

    the 1st Step for

    System Extension

    the 1st Step for

    System Extension

    Source: CIGRE Report 38-113, Paris Session 2000

    The Interconnection France-Spain a critical BottleneckThe Interconnection France-Spain a critical Bottleneck* now CE

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection How can HVDC help limiting Blackouts?

    INELFE HVDC Link

    2x1000MW

    +/-320 kV DC

    VSC

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection How can HVDC help limiting Blackouts?

    Existing

    Under Unstruction

    Planned

    HVDC EUROPE

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Conclusions

    -A Connection of SIC and SING in 500 kV AC is very likely to generate

    instalbility in both Systems

    -In case a AC transmission line shall be implemented, at least one circuit

    should be equipped with a BtB Station (Hybrid Solution)

    - An HVDC Link appears to be most economical option, i.e. on long term

    -The major argument for AC500kV may be the AC Tapoffs. But these also

    have a high cost. Connection to intermediate consumers or generators may

    be realized more economically by extensions of existing 220kV lines,

    - Detailed studies, will be necesary:

    > Power Flow Modeling

    > Short Circuit Modeling

    > Dynamic Stability Modeling

    > Transient Modeling

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection

    Muchas Gracias

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection

    Backup Slides

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING 500kV AC Single Circuit

    Simulacin 1000MW / 900MW

    L i n e a d e T r a n s m i s i o n

    - 1 1 3 3 , 9 4 M W

    - 3 7 6 , 9 5 M V A r

    1 , 3 1 k A

    1 0 0 0 , 0 0 M W

    - 4 0 3 , 9 5 M V A r

    1 , 3 2 k A

    S E C 1 1

    - 1 0 0 0 , 0 0 M W

    4 0 3 , 9 5 M V A r

    S E C 1 0

    - 1 1 3 3 , 9 4 M W

    2 2 , 5 2 M V A r

    L O 4

    - 1 0 0 0 , 0 0 M W

    - 0 , 0 0 M V A r

    I 1

    1 1 3 3 , 9 4 M W

    - 2 2 , 5 2 M V A r

    C r u c e r o ( b )

    9 4 , 5 6 %

    - 5 4 , 5 2

    C a r d o n e s ( b )

    1 0 5 , 3 6 %

    1 9 , 5 3

    C r u c e r o ( a )

    8 7 , 6 8 %

    - 3 2 , 5 3

    C a r d o n e s ( a )

    1 0 0 , 0 0 %

    0 , 0 0

    L i n e a d e T r a n s m i s i o n

    - 9 9 5 , 7 9 M W

    - 7 2 , 8 3 M V A r

    1 , 1 9 k A

    9 0 0 , 0 0 M W

    - 2 7 3 , 5 6 M V A r

    1 , 0 8 k A

    S E C 1 1

    - 9 0 0 , 0 0 M W

    2 7 3 , 5 6 M V A r

    S E C 1 0

    - 9 9 5 , 7 9 M W

    2 5 5 , 3 6 M V A r

    L O 4

    - 9 0 0 , 0 0 M W

    - 0 , 0 0 M V A r

    I 1

    9 9 5 , 7 9 M W

    - 2 5 5 , 3 6 M V A r

    C r u c e r o ( b )

    1 0 0 , 2 2 %

    - 4 3 , 7 0

    C a r d o n e s ( b )

    9 7 , 1 2 %

    1 8 , 5 7

    C r u c e r o ( a )

    9 5 , 8 9 %

    - 2 6 , 7 9

    C a r d o n e s ( a )

    1 0 0 , 0 0 %

    0 , 0 0

    1000MW

    900MW

    SC 66%

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING 500kV AC Double Circuit

    1000 MW / 100MW

    S H R 2 3

    0 , 0 0 M W

    - 1 7 5 , 0 0 M V A r

    S H R 2 0

    0 , 0 0 M W

    - 3 8 6 , 2 1 M V A r

    - 1 0 0 0 , 0 0 M W

    - 3 0 3 , 3 3 M V A r

    - 1 0 4 7 , 0 5 M W

    8 6 4 , 5 2 M V A r

    S H R 7

    0 , 0 0 M W

    - 1 7 5 , 0 0 M V A r

    L O 4

    - 1 0 0 0 , 0 0 M W

    0 , 0 0 M V A r

    I 1

    1 0 4 7 , 0 5 M W

    - 5 1 4 , 5 2 M V A r

    C r u c e r o ( b )

    1 0 2 , 4 0 %

    - 2 4 , 3 6

    C a r d o n e s ( b )

    9 3 , 4 9 %

    5 , 1 1

    C r u c e r o ( a )

    1 0 5 , 0 4 %

    - 2 0 , 1 2

    C a r d o n e s ( a )

    1 0 0 , 0 0 %

    0 , 0 0

    L i n e a d e T r a n s m i s i o n

    - 1 0 4 7 , 0 3 M W

    7 1 7 , 8 0 M V A r

    1 , 5 7 k A

    1 0 0 0 , 0 0 M W

    3 0 3 , 3 3 M V A r

    1 , 1 8 k A

    S H R 2 3

    0 , 0 0 M W

    - 1 7 5 , 0 0 M V A r

    S H R 2 0

    0 , 0 0 M W

    - 3 6 4 , 7 9 M V A r

    - 1 0 0 , 0 0 M W

    - 6 8 8 , 1 7 M V A r

    - 1 0 0 , 6 6 M W

    8 4 5 , 6 7 M V A r

    S H R 7

    0 , 0 0 M W

    - 1 7 5 , 0 0 M V A r

    S H R 5

    0 , 0 0 M W

    - 3 6 4 , 7 9 M V A r

    L O 4

    - 1 0 0 , 0 0 M W

    - 0 , 0 0 M V A r

    I 1

    1 0 0 , 6 6 M W

    - 4 9 5 , 6 7 M V A r

    C r u c e r o ( b )

    9 6 , 4 1 %

    - 2 , 5 6

    C a r d o n e s ( b )

    9 3 , 2 7 %

    0 , 4 9

    C r u c e r o ( a )

    1 0 2 , 0 9 %

    - 2 , 1 0

    C a r d o n e s ( a )

    1 0 0 , 0 0 %

    0 , 0 0

    L i n e a d e T r a n s m i s i o n

    - 1 0 0 , 6 5 M W

    7 8 7 , 9 5 M V A r

    0 , 9 8 k A

    1 0 0 , 0 0 M W

    6 8 8 , 1 7 M V A r

    0 , 8 3 k A

    1000MW

    100MW

    SC 33%

  • Energy Sector / Power Transmission Solutions

    Siemens AG 2012 May2012

    SIC-SING Connection Comparison LCC-VSC

    High Space Requirements 45 to 50 % less

    Typ. 50 % Filter/Reactive Power Requirements None

    Thyristor: very high Overload Capacity IGBT: strictly limited

    High Dynamic Performance Very high

    Classic 4.2 GW & Bulk 11 GW Rating PLUS 1,100 MVA

    1.5 % Total Converter & Station Losses close to 2 %

    Stepwise linear Independent Control of Reactive Power Fully linear

    Complex Configuration of Multiterminal Systems Simple

    No Supply of passive Networks and Black-Start Capability Yes

    Difficult Grid Access for weak AC Networks Quite easy

    Available Frequency, Voltage & POD Control Available

    FOR SIC-SING CONNECTION LCC IS A PROVEN CHOICE