Upload
p0486
View
221
Download
0
Embed Size (px)
Citation preview
7/31/2019 UNT-SVU001-EN_1002
1/16
October 2002 UNT-SVU001-EN
Owner Manual
AQUASTYLUSChilled Water Fan CoilConvertible TypeCFEA Series 50/60 Hz
50 Hz ModelsCooling OnlyCFEA 04 C0M1
CFEA 06 C0M1
CFEA 08 C0M1
CFEA 10 C0M1
CFEA 12 C0M1
CFEA 14 C0M1
CFEA 16 C0M1
CFEA 20 C0M1
60 Hz ModelsCooling OnlyCFEA 04 C0M2
CFEA 06 C0M2
CFEA 08 C0M2
CFEA 10 C0M2CFEA 12 C0M2
CFEA 14 C0M2
CFEA 16 C0M2
CFEA 20 C0M2
Cooling/HeatingCFEA 04 CEM1
CFEA 06 CFM1
CFEA 08 CBM1
CFEA 10 CHM1
CFEA 12 CJM1
CFEA 14 CJM1
CFEA 16 CKM1
CFEA 20 CLM1
Cooling/HeatingCFEA 04 CEM2
CFEA 06 CFM2
CFEA 08 CBM2
CFEA 10 CHM2CFEA 12 CJM2
CFEA 14 CJM2
CFEA 16 CKM2
CFEA 20 CLM2
AW 02092023TRA 29/10/02, 2:51 PM1
Black
7/31/2019 UNT-SVU001-EN_1002
2/16
UNT-SVU001-EN American Standard Inc.2001
General InformationCongratulations on your choice of aTrane chilled water fancoil system.These systems have been carefullydesigned and manufactured under
strict Trane Worldwide QualityStandards to provide you with yearsof comfortable, convenient cooling orheating/cooling with a minimum ofservice.
This Owner Manual is given as a guideto start-up, operation and periodicmaintenance by the user of CFEAchilled water fancoil system. It doesnot contain the full service proceduresnecessary for the continuedsuccessful operation of thisequipment. The services of aqualified service technician shouldbe employed, through themaintenance contract with areputable service company.
Read it completely before doinganything with your air conditioningsystem.
About this ManualCautions appear at appropriate placesin this instruction manual. Yourpersonal safety and the properoperation of this machine require thatyou follow them carefully. The TraneCompany assumes no liability for theinappropriate usage of the unit.
About the UnitThese CFEA units are assembled,pressure tested, dehydrated, chargedand run tested before shipment. Theinformation contained in this manual
applies to CFEA units are designed tooperate in cooling mode only and incooling or heating modes.
Trane CFEA series of chilled waterfancoil systems offer three styles ofinstallation: floor, low wall and underceiling with both LCD wireless remotecontrol or wired control. Trane CFEAseries provide flexibility and savings.Note: For model CFEA14, CFEA16and CFEA 20, there are only two stylesof installation: under ceiling and lowwall.
ReceptionOn arrival, inspect the unit beforesigning the delivery note. Specify any
damage of the unit on the deliverynote, and send a registered letter ofprotest to the last carrier of the goodswithin 72 hours of delivery. Notify thedealer at the same time.
The unit should be totally inspectedwithin 7 days of delivery. If anyconcealed damage is discovered,send a registered letter of protest tothe carrier within 7 days of deliveryand notify the dealer.
WarningWarnings are provided at appropriateplaces in this manual to indicate toinstallers, operators and servicepersonnel of potentially hazardous
situations which, if not avoided,COULD result in death or seriousinjury.
CautionCautions are provided at appropriateplaces in this manual to indicate toinstallers, operators, and servicepersonnel of potentially hazardous
situations which, if not avoided, MAYresult in minor or moderate injury ormalfunction of the unit.
Your personal safety and the properoperation of this unit require that youfollow them carefully. The TraneCompany assumes no liability forinstallations or servicing performedby unqualified personnel.
WarrantyWarranty is based on the generalterms and conditions by country. Thewarranty is void if the equipment ismodified or repaired without thewritten approval of The TraneCompany, if the operating limits are
exceeded or if the control system orthe electrical wiring is modified.
Damage due to misusage, lack ofmaintenance or failure to comply withthe manufacturers instructions, isnot covered by the warrantyobligation. If the user does notconform to the rules described inOwner Manual, it may entailcancellation of warranty andliabilities by The Trane Company.
ImportantThese instructions do not cover allvariations in systems, nor do theyprovide for every possible contingencyto be met.
Should further information be desiredor should particular problems arisewhich are not covered sufficientlyfor the purchasers purposes, thematter should be referred to yourauthorized Trane dealer.
General Information
AW 02092023TRA 29/10/02, 2:51 PM2
Black
7/31/2019 UNT-SVU001-EN_1002
3/16
3UNT-SVU001-EN
Contents
General Information 2
Control Operation 4
Wireless Remote Control 5Wired Control 9
System Operation 10
Electronic Room Thermostat 12
Maintenance 13
Troubleshooting 14
Notes 15
AW 02092023TRA 29/10/02, 2:51 PM3
Black
7/31/2019 UNT-SVU001-EN_1002
4/16
4 UNT-SVU001-EN
Infrared Remote Control
Unit Display and One-touch
Control Switch
Four lamps on the unit show operatingstatus.
1. FAN LampThis lamp lights when the fan isoperating.
2. COOLING LampThis lamp lights when the unit is inCOOL or DRY mode of operation.
3. HEATING LampThis lamp lights when the unit is inHEAT mode of operation, or heaterON in the HEAT mode of AUTOmode (light does not function onunits without electric heat)
4. TIMER LampThis lamp lights when the systemis being controlled by the timer.
One Touch Control Switch (A)This button is used for adjusting
operation without remote control unit.
This press switch is for selecting thesystem mode of operation FANCOOL DRY (HEAT)(AUTO) OFF (HEAT and AUTOare available only in Cooling/Heating Modes)
Fan speed will operate in AUTOmode; temperature setpoint will bemaintained at 24
O
C.
Note: This press switch is startedfrom COOL mode (If the system is off)and operated sequencely as above(If the system is on).The One-Touch Control mode iscancelled by the signal of the remotecontrol unit.
1
2
3
A
4
Infrared Signal Receiver
Display Panel
Control Operation
AW 02092023TRA 29/10/02, 2:51 PM4
Black
7/31/2019 UNT-SVU001-EN_1002
5/16
5UNT-SVU001-EN
Wireless Remote Control
Battery: Two AAA batteries are used inthis remote control unit.
Infrared Remote Control
Name and function of
buttons1. Infrared signal transmitter
Transmits the signal to indoor unit.2. MODE ButtonPress this button to select systemoperating modes. In cooling onlysystem, a mode is selected in asequence as FAN, COOL, DRYand back to FAN. In cooling andheating system, a mode isselected in a sequence as FAN,COOL, DRY, HEAT, AUTO andback to FAN.
3. SWEEP ButtonPress this button to activate sweepmotor to distribute air flow (notavailable in all models).
4. LOUVER ButtonPress this button to adjust thedirection of air flow.
5. POWER Button
Press this button to start operation.Press the button again to stopoperation.
6. Temperature Setting ButtonTEMP :Press this button toincrease the set temperature.TEMP :Press this button todecrease the set temperature.
7. FAN ButtonPress this button to select fanspeed.
8. SLEEP ButtonPress this button to controltemperature while sleeping.
9. CLOCK ButtonThis button is used to set theclock. If button is pressed during18.00 hrs. to 6.00 hrs., it will turn
on the back light. If there is nobutton pressed within 3 seconds,the back light will be turn off.
10. STOP ButtonPress this button to set the OFFtimer.
11. START ButtonPress this button to set the ONtimer.
12. MIN Button
This button is used to set theminute.13. HOUR Button
This button is used to set the hour.14. SEND Button
This button is used to confirm theprogramming on the remote unitto the fan coil unit.
ON OFF
2
3
4
12
13
5
6
1
7
8
9
10
11
14
AW 02092023TRA 29/10/02, 2:51 PM5
Black
7/31/2019 UNT-SVU001-EN_1002
6/16
6 UNT-SVU001-EN
Wireless Remote Control
Indicators on Infrared
Remote Control
ON OFF
1
2
35
6
7
8
4
1. ClockDisplays the current time when thehandset is under POWER OFFstatus.
2. Timer START
The time set for timer on operationis indicated.
3. Timer STOPThe time set for timer off operationis indicated.
4. Transmission IndicatorThis transmission indicator lightswhen remote control transmitssignals to the indoor unit.
5. SLEEP ModeDisplayed by pressing the SLEEPbutton. Press the SLEEP buttonagain to disappear.
6. Temperature SettingDisplays the temperature setting(15
O
C to 30O
C) When the handset isunder POWER ON status.Note : No temperature settingdisplay when FAN Mode isselected.
7. Fan SpeedDisplays the selected fan speed.Fan speed level, low (LOW),medium (MED), high (HIGH),auto (AUTO) will be indicated.
8. System ModeDisplays the current operationmode. In cooling only (FAN, COOLor DRY). In cooling and heatingsystem (FAN, COOL, DRY or HEAT).
System Operating
Selection
FAN Only System Operation
- Press POWER button (the displaypanel shows the previous settings).- Press MODE button to select the
system operating mode, FAN modewill be shown on the display.
- Press FAN button to select any fanspeed. The FAN display will show
LOW, MED, HIGH or AUTOaccording to fan speed level, low,medium, high and auto.
COOLING System Operation- Press POWER button (the display
panel shows the previous settings).- Press MODE button to select the
COOL operating mode, COOLmode will be shown on the display.
- Press either TEMP or TEMP button to set the desired room
temperature. Temperature setrange is 15
O
C to 30O
C.- Press FAN button to select any fan
speed. The FAN display will showLOW, MED, HIGH or AUTO
according to fan speed level, low,medium, high and auto.
DRY System Operation- Press POWER button (the display
panel shows the previous settings).- Press MODE button to select the
DRY operating mode, DRY modewill be shown on the display.
- Press either TEMP or TEMP button to get the desired roomtemperature setting at theindication. Temperature set rangeis 15
O
C to 30O
C.Note : Fan speed cannot be changed
when DRY Mode is selected.
HEATING System Operation(Heating/Cooling Models)- Press POWER button (the display
panel shows the previous settings).- Press MODE button to select the
HEAT operating mode, HEATmode will be shown on the display.
- Press either TEMP or TEMP button to set the desired roomtemperature. Temperature setrange is 15
O
C to 30O
C.
- Press FAN button to select any fanspeed. The FAN display will show
LOW, MED, HIGH or AUTOaccording to fan speed level, low,medium, high and auto.
AUTO System Operation(Heating/Cooling Models)- Press POWER button (the display
panel shows the previous settings).- Press MODE button to select theAUTO operating mode, AUTOmode will be shown on the display.
- Press either TEMP or TEMPbutton to set the desired roomtemperature. Temperature setrange is 15
O
C to 30O
C.- Press FAN button to select any fan
speed. The FAN display will showLOW, MED, HIGH or AUTOaccording to fan speed level, low,medium, high and auto.
- The system will automaticallyswitch between cooling mode andheating mode to maintain desiredtemperature setting.
AW 02092023TRA 29/10/02, 2:51 PM6
Black
7/31/2019 UNT-SVU001-EN_1002
7/16
7UNT-SVU001-EN
Wireless Remote Control
Setting ClockTo set clock, press CLOCK buttonuntil CLOCK symbol is blinking.The current time value can be set bypressing HOUR or MIN (minute)
button.
Note : During the clock symbol isblinking (the time valve has not beenchanged), if there are no other buttonspressed within 10 seconds, the LCDdisplay will return to show settingtemperature when the handset isunder POWER ON status, or to showcurrent time value when the handsetis under POWER OFF status.
Timer OperationOnce you select the timer operation,the settings are saved in the remotecontrol. Thereafter, the air conditionerwill start operating under the sameconditions when you simply push thePOWER button of the remote control.
Setting STOP TimerYou can set the STOP timer to stopthe unit automatically at any desiredtime up to 24 hour ahead.- Press STOP button to set time to
turn the unit OFF. The OFF symbolis starting to blink.
- Press HOUR or MIN buttons tochange the time (pass this step, ifno time change is required).
At this stage, if there are no otherbuttons pressed within 10 seconds,the LCD display will return to showsetting temperature or current timevalve. No setting is changed.
- Press SEND or STOP buttonsto transmit the signal to the airconditioner. The set time will stopblinking.
- The unit will stop automatically atset time of OFF timer.
- To cancel the STOP timer, pressSTOP button again.
Setting START TimerYou can set the START timer to startthe unit automatically at any desiredtime up to 24 hour ahead.- Press START button to set time to
turn the unit ON, the ON symbol isstarting to blink.- Press HOUR or MIN buttons to
change the time (pass this step, ifno time change is required).
At this stage, if there are no otherbuttons pressed within 10 seconds,the LCD display will return to showsetting temperature or current timevalve. No setting is changed.
- Press SEND or START buttons totransmit the signal to the airconditioner. The set time will stopblinking.
- The unit is now standby for startingautomatically at set time of STARTtimer.
- To cancel the START timer,press START button again.
Note : In case of power failure,the START/STOP timer will beautomatically cancelled as there isno electricity in the air-conditioner.(But the set time on the remote unitis still displayed due to the batteries).If any button or the remote unit ispressed when the electricity is backto normal, this feature will bere-activated.
AW 02092023TRA 29/10/02, 2:51 PM7
Black
7/31/2019 UNT-SVU001-EN_1002
8/16
8 UNT-SVU001-EN
Wireless Remote Control
SLEEP ModeThis feature automatically adjusts thetemperature setting to provideincreased comfort and save energy(The SLEEP display on LCD will
disappear after 1 hour).
COOLING Mode- Press SLEEP button, one hour
after pressing, the air conditionerwill automatically raise the settemperature by 1
O
C.
SWEEP OperationThe SWEEP function will operate ineither cooling or heating mode torapidly distribute conditioned airinto the room.
- The supply air grille will be fullyclosed when the unit is off.- When the unit is turned on, the
grille will open to the fully openposition.
- After the unit has been turned on,pressing the SWEEP button willsweep the supply air grille backand forth to rapidly distribute andcool (or heat) the room.
- If the unit is in SWEEP mode,pressing the sweep button willreturn the grille to the fully openposition.
- Press the POWER button while theunit is in operation, will turn off theunit and the supply air grille willautomatically close.
LOUVER OperationThe direction of the airflow can becontrolled.- Press LOUVER button to adjust the
angle of the blade to control thedirection of the air flow.
Note : The sweep and louveroperations are optional functions ofCFEA04-CFEA08. These operationsare not available in the modelsthat have cooling capacity more than24,000 Btu.
HEATING Mode- Press SLEEP button, one hour
after pressing, the air conditionerwill automatically reduce the settemperature by 1
O
C.(The SLEEP display on LCD willdisappear after 1 hour).
0 1 2 3 4 5 6 7 8 9 10 11 12-2
OC
-1OC
SET POINT
START
NORMAL SLEEP
HOUR
+1OC
+2OC
SLEEP (COOLING MODE)
By pressing SLEEP button, the unit will operate at SLEEP FUNCTION it will
automatically return to normal operation when the air-conditioner is switched
off and on again.
0 1 2 3 4 5 6 7 8 9 1 0 11 12
START
NORMAL SLEEP
HOUR
SLEEP (HEATING MODE)
By pressing SLEEP button, the unit will operate at SLEEP FUNCTION it will
automatically return to normal operation when the air-conditioner is switched
off and on again.
-2OC
-1OC
SET POINT
+1OC
+2OC
AW 02092023TRA 29/10/02, 2:51 PM8
Black
7/31/2019 UNT-SVU001-EN_1002
9/16
9UNT-SVU001-EN
1.FanThree fan speed (high, medium,low) can be selected. The fanspeed can also be put in AUTOfan mode. It will be changed
automatically from high to mediumand low according to the differencebetween room and settingtemperature.
2. Power On/OffPress POWER button will turn on/off the air conditioner. When turnedon, it will operate according to thelast program setting.
3. Temperature SettingThe temperature can be set in therange of 15
O
C - 30O
C.4.Sleep
The facility to raise up the settingtemperature 1
O
C (in Cool mode)for the purpose of comfort andenergy saving.
5. Operating ModePress MODE button to select
system operating modes. The airconditioner can be put in 2 modes(COOL and FAN) for cooling onlymodel. And 3 modes (COOL, HEATand FAN) for cooling/heating model.
6.TimerThe facility to turn on/off the airconditioner is 15 hours in advance.TIMER OFF To set timer off bypressing TIMER button during airconditioning is on, TIME LED willblink and will show last hour timesetting in blinking light. PressingHOUR or HOUR to increaseor decrease hour digit (between 1to 15 can be set).TIMER ON Using same procedureto set timer off except press TIMERbutton during air conditioner is off.
7. Toggle OC/OF
The facility to change TemperatureDisplay from
O
C toO
F or fromO
Fto
O
C. By pressing TEMP+ andTEMP- button at the same timefor 5 seconds.
Wired Control
A
HOUR TEMP
HOUR
TemperatureDisplay
Hour SettingButton
Timer Button
Fan Button
Power Button
TemperatureSetting Button
Sleep Button
For Cooling/Heating Model
Mode Button
TEMP
TIMER
COOL
FAN
HEAT
SLEEP
MODE
0 1 2 3 4 5 6 7 8 9 1 0 11 12-2
OC
-1OC
SET POINT
START
NORMAL SLEEP
HOUR
+1OC
+2OC
SLEEP (COOLING MODE)
By pressing SLEEP button, the unit will operate at SLEEP FUNCTION it will
automatically return to normal operation when the air-conditioner is switched
off and on again.
0 1 2 3 4 5 6 7 8 9 10 11 12
START
NORMAL SLEEP
HOUR
SLEEP (HEATING MODE)
By pressing SLEEP button, the unit will operate at SLEEP FUNCTION it will
automatically return to normal operation when the air-conditioner is switched
off and on again.
-2OC
-1OC
SET POINT
+1OC
+2OC
AW 02092023TRA 29/10/02, 2:51 PM9
Black
7/31/2019 UNT-SVU001-EN_1002
10/16
10 UNT-SVU001-EN
System Operation
Notes: If TIMER LED is off, HOUR and
HOUR button do not function. If TIMER LED is on, pressing
HOUR and HOUR button
will change display time setting toshow hour set left with blinkinglight. If press HOURand HOURbutton will change display to newtime setting.
If the air conditioner stops bypower failure, setting of timer on/offwill be cancelled.
If POWER button is pressed duringsetting if timer, setting of timeron/off will be cancelled and remotewill turn on/off air conditioner asnormal.
If TIMER button is pressed againduring setting of time (TIMER LEDis lit), setting time will be cancelled.
Display Unit
The following LEDs are used toindicates the status,
A LED (in Fan Button) shows whenthe fan speed is put in AUTO mode,SLEEP LED shows the system isput in sleep mode,TIMER LED shows when set the timeron/off. FAN/COOL/HEAT LED showsthe operating mode of the airconditioner.
Temperature Display (7-segmentLED, 2 digits) show- The room temperature.- The setting temperature while
blinking.- RE, show the room sensor is
open or short circuit.- FE show the freeze sensor is
open or short circuit.- HF show the heating system is
supposed to be fail. (For Cooling/Heating model)
- Fr show the evaporator coil isfreeze.
When press the Fan Button to selectthe fan speed. The display show thestatus below.- F3 show the fan speed is high.- F2 show the fan speed is
medium.- F1 show the fan speed is low.- FA show the fan speed is put inAUTO mode.
System Features1. Watchdog
There is a circuit in the system towatch the operation of themicroprocessor.
2. Non-Volatile Memory(Auto Restart)
After power interruption, the controlwill resume its operation with samesetting parameters except thoserelated to the time.
3. Pre-heat/Post-heat (Heat Model)The facility to prevent the fan coilblowing cold draught when theindoor coil temperature is low.
4. Freeze Function (Optional)The facility to stop the compressorif the indoor coil temperature isbelow 0
O
C.
Operating PrecautionsThis system must be installed properlyby a qualified installer in accordancewith installation instructions.
Temperature setting is adjustedback and forth.
ON/OFF switch is turned ONandOFF.
Room temperature reaches theset point.
Power failure.
Once any of the above conditionsoccurs, the anti-recycle timer willstart preventing the operation ofthe outdoor unit for approximately3 minutes.
Freeze ProtectionThe system is protected against lowindoor coil temperatures. Undercertain conditions, the COOL/DRYLED will blink indicating the protective
function has been activated. There isno need to adjust the system.
Stop the air conditioner at onceif any the following occurs:- The power cord is too hot to be
touched by hand.- The insulation of the power cord is
exposed at any point- The fuse is blown or circuit breaker
trips frequently.- The functions of the switches are
inaccurate.
Operating air conditioner safety.- Do not insert a bar or similar
object into the supply air outlet.In particular, advise small childrennot to insert anything in the grille.
- Do not pour water directly on theair conditioner to clean it. If theair conditioner is operating as wet,grounding may occur, damagingthe unit.
- Adjust the air flow so it does notblow directly on room occupants.
- Do not use flammable sprays nearthe air conditioner because ofdanger of fire.
- Do not use a steel or copper wirein place of fuses.
AW 02092023TRA 29/10/02, 2:51 PM10
Black
7/31/2019 UNT-SVU001-EN_1002
11/16
11UNT-SVU001-EN
Adjust Air Flow Direction- The supply air grille may be
adjusted left, right, up or downmanually.
- Adjust the air flow direction
properly, otherwise, it may causediscomfort and make the roomtemperature uneven.
Adjust Air Flow Direction(with sweep option)- The sweep motor will sweep the
supply air grille upward anddownward.
- For left and right air flow, thesupply air grille can be adjustedmanually.
- Do not inspect or service theair conditioner while it is operating.Turn off the power supply beforedoing any inspection or servicework.
- The power cord should be keptaway from furniture with sharpcorners. It may cause fire orelectric shock.
- When the air conditioner will notused for a long time, be sure to turnOFF the power supply.
If you have any questions or problemswith your air conditioning system,please consult your nearestTrane dealer.
Up
Down
Right
Left
System Operation
AW 02092023TRA 29/10/02, 2:51 PM11
Black
7/31/2019 UNT-SVU001-EN_1002
12/16
12 UNT-SVU001-EN
16oC
22
27
30
POWER
ON
OFF
FAN
COOL
WARM
3
1
2
1) Power ButtonPush power button to ON positionto turn on the air condition, andpush to OFF position to turn offthe air condition.
2) Fan ButtonThree fan speed (high, medium,low) can be selected by push thebutton to the desired position.
3) Temperature SettingTemperature setting can be set inthe range of 16C - 30C byrotating the temperature settingknob to the position .
Electronic Room Thermostat
AW 02092023TRA 29/10/02, 2:51 PM12
Black
7/31/2019 UNT-SVU001-EN_1002
13/16
7/31/2019 UNT-SVU001-EN_1002
14/16
14 UNT-SVU001-EN
Troubleshooting
Before calling for service,please check the following.
The air conditioner does notoperate at all:
- Check if the control ON/OFFswitch is OFF. Turn the switch toON.
- Check whether the fuse has beenblown or circuit breaker thrown.Set the ON/OFF Control Switch toOFF, and turn on the circuit breakeror replace to a new fuse.
- Check whether the power supplyis interrupted. Wait until the poweris resupplied and then operate theair conditioner.
Cooling is insufficient:- Check whether the air filter is
clogged. Clean it.- Check whether the thermostat
setting is too high. Set thethermostat to lower temperature.
- Check whether windows or doorsare opened. If opened, close them.
- Check whether there are sourcesof heat in the room, cooling is lesseffective.
- Check whether the return air grilleor the supply air grille on theindoor unit and outdoor unitare blocked. If they are blocked,remove obstacles to permit air
passage properly.- Check whether the fan speed is setat low. Set the fan switch fromLOW to MED or HIGH
Heating is insufficient:- Check to see if the air filters are
clogged with dust or debris. Cleanthe air filters.
- Check to see if the thermostatsetting is too low. Set thethermostat a higher temperature.
- Check to see if windows or doorsare open. If they are open, close.
- Check to see if the return air grilleor the supply air grille on theindoor unit are blocked. If they areblocked, remove obstacles topermit air passage properly.
- Check to see if the fan speed is setat low setting. Set the fan switchfrom LOW to MED or HIGH
AW 02092023TRA 29/10/02, 2:51 PM14
Black
7/31/2019 UNT-SVU001-EN_1002
15/16
15UNT-SVU001-EN
Notes
AW 02092023TRA 29/10/02, 2:51 PM15
Black
7/31/2019 UNT-SVU001-EN_1002
16/16
Trane Thailand
7th Floor, Ploenchit Center Building
2 Sukhumvit Road, Klongtoey
Bangkok 10110
Amair Limited
35 Mu 8, Poochaosamingprai Road
Samrong Tai, Samutprakarn 10130
http://www.trane.com
An American Standard Company
Literature Order Number UNT-SVU001-EN 0701
Supersedes UNT-SVU001-EN 0999
Stocking Location Bangkok, Thailand
35 8 . .. . 10130
Since The Trane Company has a policy of continuous product and product data i mprovement,
it reserves the right to change design and specifications without notice.
AW 02092023TRA 29/10/02, 2:51 PM16
Black