HART highway addressable remote transducer Ravikumar Koturwar 13MAC0038 Rahul S Kore 13MAC0041 Parth M Mehta 13MAC0048

HART

Embed Size (px)

DESCRIPTION

Highway Addressable Remote Transducer (HART) is an industrial standard protocol which is widely well established and used by most of the industries.Among the 45-50 Million industrial devices,48% devices are non-smart devices and 52% devices are smart devices.Among the 52% means around 25-26 million smart devices 26% means near about 12-13 million devices are HART based devices.

Citation preview

Page 1: HART

HARThighway addressable remote transducer

Ravikumar Koturwar 13MAC0038Rahul S Kore 13MAC0041Parth M Mehta 13MAC0048

Page 2: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 1

Page 3: HART

Why its Popular nowThe HART protocol directly contributes to these business goals by providing cost savings in:

Commissioning and installation

Plant operations and improved quality

Maintenance

Analog 4–20 mA and digital signals provide flexibility not available with any other communication technology.

Hand Held Communicators are often used to perform device set-up, calibration, commissioning and periodic maintenance

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 2

Page 4: HART

Improved plant operations

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 3

Page 5: HART

Operational Flexibility

Multi-master Operation?

Primary master ---- control system

Secondary master ---- A hand-held communicator or a maintenance computer.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 4

Page 6: HART

Instrumentation investment protection

Wiring, analog controllers, barriers, analog or smart instrumentation

exists widely

The HART communication protocol enables you to retain your previous investments in existing hardware and personnel. VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 5

Page 7: HART

Digital communication

The HART protocol enhances the capabilities of digital instruments by providing communication access and networking

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 6

Page 8: HART

HART Vs. Fieldbus

HART is compatible with existing wiring in older plants.

Hart is understood, accepted and appreciated by virtually everyone involved.

Fieldbus costs a lot more to implement, especially for existing equipment.

Lot of instruments not radially available with Fieldbus.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 7

Page 9: HART

HART specifications?

Physical form of transmission

Transaction Procedures

Message structures

Data formats

Set of commands to perform required operation.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 8

Page 10: HART

Communication Modes of HART?

Master Slave Mode (Poll---Response Mode)

Maximum communication speed --- 2 messages/sec.

Configuration ---- Point-to-point or Multi-point

Master sends command (request) , slave responds (replies)

Request

Reply

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 9

Page 11: HART

Burst Mode ( Broadcast Mode)

Slave transmits messages continuously (e.g. values of a measurand).

The communication speed --- 3 message/sec.

A slave device repeatedly sends a data message.

Used for fast updation of the value of a measured variable

Continuous ReplyVIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 10

Page 12: HART

HART Signal Levels?

HART protocol specifies that master device transmit a voltage signal whereas slave device transmits a current signal.

The current signal is converted in to corresponding voltage by a loop load resistor(250 ohms), so all devices use voltage sensitive receiver circuits.

The wave shape is sinusoidal, but trapezoidal waveform is acceptable. A square wave is not acceptable.

Master Slave Operation?

The each message transaction is originated by the master station, the slave device only replies only when it receives a command message.

The reply from the slave device acknowledges that the command has been received and may contain data requested by the master.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 11

Page 13: HART

Different HART networks?

Point-to-point Mode

Both analog and digital communications are supported.

4–20 mA signal is used to communicate one process variable.

Additional process variables, configuration parameters, and other device data are

transferred digitally using the HART protocol

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 12

Page 14: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 13

Page 15: HART

Multidrop Mode

Only digital communication is supported

Requires only a single pair of wires

In case safety barriers and an auxiliary power supply for up to 15 field devices

All field device polling addresses are >0, and the current through each device is fixed to a minimum value (typically 4 mA).

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 14

Page 16: HART

VIT Control and Automation’13-14

15

Page 17: HART

Different Groups of HART commands?

Universal : Provides functions which are implemented in all field devices. Examples : Read model Read serial number Read range

Common Practice : Provides functions common to many field devices but not all. If a device uses these functions, these commands should be used to perform them.

Examples : Read (up to 4) variables

Perform calibration check

Perform self-test

Device specific : Provides functions which are more or less unique to a particular filed device .

Examples : Select 0C/0F (temperature sensor)

Tune a control parameter (control device)

Write alarm set point (relay)

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 16

Page 18: HART

Command Summary

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 17

Page 19: HART

Types of Frame Formats in HART protocol?

Short frame format ---- Older HART instruments(Version4) used short frame format. In this the address of the slave device is ‘o’.

Long frame format ---- HART version 5 introduced ‘Long frame format”. In this the address of the slave device is world wide unique identifier.

It is a 38 bit number derived from the manufacturer code.

It contains the device code and device id no

Long frame format gives extra security against the possible reception and acceptance of command meant for another device, either due to external interference or due to excessive cross talk

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 18

Page 20: HART

Some More Points

pass-through feature?

DD?

Interoperability?

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 19

Page 21: HART

Wireless HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 20

Page 22: HART

Introduction

Wireless HART is a wireless mesh network communication protocol.

It is designed to meet the needs for process automation applications

It is a KEY part of the HART field communication protocol Version 7

Less than 10% of the installed HART instruments have a direct communications link back to a host system.

The addition of low-cost wireless connectivity provides a pathway for remote host systems to read process and maintenance information from field instruments, both old and new.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 21

Page 23: HART

Wireless HART Network Structure

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 22

Page 24: HART

Wireless Mesh

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 23

Page 25: HART

Time Synchronization

Report by Exception – Time- and Condition-based Alerts

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 24

Page 26: HART

Time Stamp

synchronized clock enabling it to transmit data at the correct time.

Used to stamp time and date

Wireless Co-existence

Uses channel assessment and short message sizes to coexist with neighboring networks

Wireless Diagnostics

Ensures the health of the network

Include indicators of battery life remaining, devices present, network join attempts and other network management indicators.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 25

Page 27: HART

Wireless Security

Join Key

Unique Message Integrity Code (MIC)

Message Encryption

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 26

Page 28: HART

Loop Testing

No 4 to 20 mA signal

It checks that the process data is displayed correctly at the host and also tests other control functions.

Wireless HART Adapter

New HART device can be added to wired device to provides wireless Feature

Loop - PoweredVIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 27

Page 29: HART

WIRELESS NETWORK

28

Page 30: HART

PART 2

FSK

HART signal

HART protocol

MUX

ComparisonVIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 29

Page 31: HART

CHARACTERISTICS

Simultaneously supports two communications channels. » 4-20mA "analog" communications and

» Modulated two-way "digital" communications.

Additional process data in Multi-Variable devices used to improve plant operation

Field devices can continuously publish their process data. » Operators alerted to impending problems before negative impact to the process = Real time device diagnostics.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 30

Page 32: HART

FSK

Bell 202 Frequency Shift Keying (FSK) standard to superimpose digital communication signals at a low level

on top of the 4-20mA.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 31

Page 33: HART

HART SIGNAL in Physical layer

HART allows additional information to be carried on the same pair of wires with

the 4-20 mA Analog Signal

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 32

Page 34: HART

TWO COMMUNICATION CHANNEL

4-20mA "Analog" Channel

HART"Digital"Channel

4-20mA Analog support large part of Protocol Specifications One-way communication of one process value Simple Low Pass Filter isolates 4- 20mA signal

Compliments 4-20mABased on Analog Telephone Modems

» Long Cable Runs» High Noise Immunity» You can "hear" HART

Two-way Communications

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 33

Page 35: HART

Example

Fig : Two Communication Channels

• Connecting a PC to a HART device or network

• PC application development tools > PC configuration software

• Universal handheld communicator >275 Universal

• Reading HART data into non-HART systems

• Commissioning HART networks > HART multidrop networks

• Control system interfaces > Control in field devices

• Multiplexers

• Device status and diagnostics

• Intrinsic safety(IS)

The following sections contain information that can help you to get the most from your HART system:

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 34

Page 36: HART

CABLE LENGTH

TABLE: Allowable cable lengths for(#18 AWG) shield twisted pair

Theoretical Length max. :

Affected by: electrical characteristics ( mostly Capacitance)

& Combination of connected devices

It is also a good idea to buy a cable designed for HART. Belden 3105A is an example of such a cable.

3,000 meter (10,000 ft)

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 35

Page 37: HART

HART PROTOCOL LAYERS

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 36

Page 38: HART

• Controlled by HCF • Open and Available to Anyone• Easy-to-Read Language• Consistent and well-defined terms

Organization of HART SpecificationsVIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 37

Page 39: HART

Protocol Structure

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 38

Page 40: HART

LONG FRAME FORMAT

39

VIT Control and Automation’13-14

Page 41: HART

Packet Structure

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 40

Page 42: HART

RESPONSE

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 41

Page 43: HART

General device status is always returned with COMMAND3

2 bytes of status info.

HART COMMAND 3

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 42

Page 44: HART

STATUS MESSAGES ARE:

Status Messages

Field device malfunction (Bit 7)

Configuration changed (Bit 6)

Cold start (Bit 5)

More status available (Bit 4)

Analog output current fixed (Bit 3)

Analog output saturated (Bit 2)

Non-primary variable out of limits (Bit 1)

Primary variable out of limits (Bit 0)

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 43

Page 45: HART

COMMAND 48

Device specific information is always returned with COMMAND48

25 bytes of additional status information

*Not necessary to use all the bytes Ex. Honeywell STT250 uses only first 3 bytes.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 44

Page 46: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 45

Page 47: HART

MultiplexersTo interface numerous HART devices

Support point-to-point and all-digital (multidrop)

Communication between a multiplexer and host depends on the multiplexer capabilities

RS232C, RS485, Modbus, TCP/IP Ethernet

can be used as primary I/O front end for aHART-based control or monitoring system

When installing HART multiplexer systems, the following capabilities should be considered:

o Number of HART channels supported o Number of HART channels that share a HART modem o Burst mode supporto Multidrop supporto Method of communication with the host computer or control system

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 46

Page 48: HART

1. PARALLEL MONITORING WITH A MULTIPLEXER

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 47

Page 49: HART

PC acts as the host, providing the human-machine interface & perform high-level functions.

Mux passes HART commands from the host computer to the field devices.

continuously monitors the field devices, reports the current readings and instrument status to the host,

Figure: HART Multiplexer as the Primary I/O System

2. MULTIPLEXER AS THE PRIMARY I/O SYSTEM

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 48

Page 50: HART

Multiplexer refresh time > function of no. of devices connected per channel

Refresh time = 0.8sec / device / modem

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 49

Page 51: HART

3. CONTROL FIELD DEVICES

Figure: Transmitter with PID (HART Slave)

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 50

Page 52: HART

Wireless HART vs. Bluetooth

vs. Zigbee

Range

Data security = Reliable message delivery

Industrial grade robustness = Industry acceptance

Reliability.

*No HART device use Bluetooth connectivity with data load.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 51

Page 53: HART

No frequency diversity > Entire network shares same static channel

Static Channel also susceptible to interference with wireless LAN

Makes it susceptible to both intended and unintended jamming

Can stop entire network communication

Designed from start for robust and secure Communication

Network works 24*7 > no option to turn it completely off

Mesh networking with graph routing > provide redundancy and self healing

ZigBee

Wireless HARTVIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 52

Page 54: HART

Comparison at layer level

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 53

Page 55: HART

Versions

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 54

Page 56: HART

Industry App’sPART 3

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 55

Page 57: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 56

Page 58: HART

Reading HART Data into Non-HART Systems

Many HART products are able to perform more than one measurement oroutput function (e.g., make multiple process measurements, calculateprocess information, and provide positioner feedback information). All ofthis information can be easily accessed digitally. However, existingcontrollers or interface equipment may not have the ability to read digitalHART data. Products are available that can read HART digital signals andconvert them to analog or contact information, which enables anytraditional analog/digital I/O to take full advantage of the benefits ofHART-communicating devices.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 57

Page 59: HART

The Tri-Loop module monitors a HART loop for a bursting message andconverts three of the four possible variables in HART communicator.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 58

Page 60: HART

The site programmable alarm( SPA )module continuously communicates with any HART-capabledevice and provides contact closure outputs (alarm trips) based on theinformation received (Figure 14). For example, the SPA can be configured to monitor the device-status information inherent in the HART communication protocol and trigger events such as local on/off applications or alarms. The SPA can also initiate emergency shutdown action if problems are detected with a field device in critical loop applications

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 59

Page 61: HART

Industrial Application

Many companies in a wide variety of industries have already realized the advantages of using the HART communication protocol. This section describes some applications in detail and outlines the tangible benefits that result.

The applications have been grouped into the following sections:

Inventory-management applications

Cost-saving applications

Remote-operation applications

Open-architecture applications

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 60

Page 62: HART

Inventory-Management Applications

Accurate measurements for inventory management are essential in all industries. The HART communication protocol enables companies to make sure inventory management is as efficient, accurate, and low cost as possible.

Tank level and inventory management is an ideal application for a HART multidrop network . The HART network digital update rate of two PVs per second is sufficient for many tank-level applications. A multidrop network provides significant installation savings by reducing the amount of wiring from the field to the control room as well as the number of I/O channels required.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 61

Page 63: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 62

Page 64: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 63

Page 65: HART

UNDERGROUND PETROLEUM

STORAGE WITH HART COMMUNICATION FOR

ACCURACY

Underground salt caverns are frequently used for crude oil storage. One customer pumps oil from barges into the storage caverns. An ultrasonic flow-meter records the total flow. To get the oil out of the caverns, a brine solution is pumped into the cavern through a magnetic flow-meter. Brine and crude oil flowing in both directions are measured and reported to the DCS using the HART communication protocol for accuracy.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 64

Page 66: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 65

Page 67: HART

Cost-saving applications

A Texas wastewater treatment plant replaced stand-alone flow meters and chart recorder outstations that required daily visits for totalization with a HART system. HART-based magnetic flow meters were multidropped into HART RTUs to create a cost-effective SCADA network. The use of HART technology reduced system and cable costs, enhanced measurement accuracy, and eliminated time-consuming analog calibration proceduresVIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 66

Page 68: HART

A consumer appliance manufacturer used the networking capability of the HART protocol to ensure level, flow, and pressure HART multidrop provided substantial wiring and installation savings as well as digital accuracy with the elimination of the analog to digital (A/D) and digital to analog (D/A) conversions of the instrument and PLC I/O. Figure shows pressure transmitters connected to a PLC via smart transmitter interface multiplexers.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 67

Page 69: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 68

Page 70: HART

Remote-Operation Applications

Choosing the HART communication protocol for all-digital communicationin a wide-area network enabled one company to have real-time monitoringand control, access to diagnostics, and maintenance capabilities—all from aremote location.

Each platform’s RTU provided a link to approximately 50 temperature,pressure, and flow transmitters. The RTU used the multi-mastercapability of the HART protocol to enable the second RTU to act as a hotstandby, which monitored activity and was able to take over if a failureoccurred. The RTUs provided links with the emergency and safety systemsand a local interface for maintenance personnel. The Modbus protocol wasused for communication to the central SCADA system

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 69

Page 71: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 70

Page 72: HART

In a Venezuela gas-lift project, HART multidrop technology was used for remote operation of offshore gas-lift production wells at considerable savings:

30% decrease in installation costs

16:1 reduction of input modules

Reduced cost of I/O cards in the RTU

Remote re-ranging

Remote access to the transmitter status for improved process uptime

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 71

Page 73: HART

Open-Architecture Applications

The best way to judge the openness of a communication protocol is by thenumber of products supported. By this standard, the HART protocol isperhaps the most open of any field-communication protocol availabletoday.

In a major refinery expansion, an oil company weighed the advantages ofusing either a proprietary system or a HART-based system. The resultsindicated that the company could use HART digital instruments in 92% oftheir applications, compared to only 33% with the proprietary system.Choosing HART products resulted in an incremental $23,000 in savingsdue to commissioning efficiencies and ongoing maintenance and diagnosticcapabilities.

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 72

Page 74: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 73

Page 75: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 74

Page 76: HART

Intrinsic Safety

Intrinsic safety (IS) is a method of providing safe operation of electronicprocess-control instrumentation in hazardous areas. IS systems keep theavailable electrical energy in the system low enough that ignition of thehazardous atmosphere cannot occur. No single field device or wiring isintrinsically safe by itself (except for battery-operated, self-containeddevices), but is intrinsically safe only when employed in a properlydesigned IS system.

HART-communicating devices work well in applications that require ISoperation. IS devices (e.g., barriers) are often used with traditionaltwo-wire 4–20 mA instruments to ensure an IS system in hazardous areas.With traditional analog instrumentation, energy to the field can be limitedwith or without a ground connection by installing one of the following ISdevices

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 75

Page 77: HART

Shunt-diode (Zener) barriers that use a high-quality safety groundconnection to bypass excess energy

Isolators, which do not require a ground connection, that repeat theanalog measurement signal across an isolated interface in the safe-sideload circuit Both Zener barriers and isolators

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 76

Page 78: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 77

Page 79: HART

When designing an IS loop using shunt-diode barriers, two additionalrequirements must be considered:

1. The power supply must be reduced by an additional 0.7 V to allow

headroom for the HART communication signal and yet not approachthe Zener barrier conduction voltage.

2. The load resistor must be at least 230 Ω (typically 250 Ω).VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 78

Page 80: HART

HART is a backward compatible enhancement to 4-20mA instrumentation that allows two way communication with smart, microprocessor-based field devices.

Continuously Validate Integrity of Control Information –Ensure accuracy of system data/ Automatically detect any deviation between device and system

Continuous Real Time Diagnostics– Device Problems/ Loop Current Faults– Device Needs Maintenance

Unlock additional information in Multi-Variable devices

CONCLUDE

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 79

Page 81: HART

Wireless HART is designed based on a set of funda- mental requirements: it must be simple (e.g., easy to use and deploy)

Self-organizing and self-healing.

flexible (e.g., support different applications)

Scalable (i.e., fit both small and large plants)

Reliable, secure, and support existing HART technology (e.g., HART commands, configuration tools, etc.)

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 80

Page 82: HART

VIT Control and Automation’13-14

VIT UNIVERSITY, SELECT 81

Page 83: HART

Questions??

Ravikumar Koturwar 13MAC0038Rahul S Kore 13MAC0041Parth M Mehta 13MAC0048