    Datasheet

    The PDR is an equipment ground faultprotection device that combineshydraulic/magnetic circuit breaker andoverload and short circuit protection andground fault protection. This breakersenses and guards against faults toground using a state of the art integrat-ed circuit. This technology detects faultsand when a fault occurs, the breakertrips and an LED illuminates. The LEDgives a clear indication that the trip

    occurred as a result of leakage. This pro-tection helps prevent serious equipmentdamage and fire.

    Our Circuit Breakers are designed accordingto railway regulations:

    - IEC 60077 - 1/2/3

    - NF F62-001 - 1/2/3

    - EN 45545-2 & NF F16-101/102(fire and toxic regulations)

    Proven Reliability

  • 7/30/2019 Pdr Series

    2/9

    Genaral tecnical dats

    ElectricalMaximum Voltage AC, 480 WYE/277 VAC, 50/60 HzCurrent Ratings 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 20.0, 25.0, 30.0, 35.0, 40.0 & 50.0 amps.

    For other ratings, consult factory.Insulation Resistance Minimum: 100 Megohms at 500 VDCDielectric Strength 1960 VAC, 60 Hz for one minute between all electrically isolated terminals.Resistance, Impedance from Line to Load Terminal (Values Based on Series Trip Circuit Breaker)

    Leakage to groundStandard Must Trip Leakage Current Ratings 7, 10, 15, 30, 50 & 100 milliamps. For other ratings, consult factory.Trip Time 300 ms Max. @ 100%, 40ms Max. @ 500% of must trip leakage current.Test Button On breaker face above actuator.Leakage Trip Indicator Red LED on breaker face above actuator.

    MechanicalEndurance 10,000 ON-OFF operations @ 6 per minute; with rated Current & Voltage.Trip Free All PDR equipment leakeage circuit breakers will trip on overload or leakage to

    ground, even when actuator is forcibly held in the ON position.

    PhysicalNumber of Poles 2, 3 & 4 PolesLength 106.7 mm (4.2 inches) (included switched or unswitched neutral)Width 2-pole: 76.2 mm (3.0 inches)

    3-pole: 95.3 mm (3.75 inches)4-pole: 114.3 mm (4.5 inches)

    Depth 63.5mm (2.5 inches)Weight 2-pole: 453.6 g (16.0 oz.)

    3-pole: 606.7 g (21.4 oz.) 4-pole: 762.6 g (26.9 oz.)Standard Colors Housing - gray; Actuator - black, red, or whiteMounting Front Panel or Standard 35mm Symmetrical DIN Rail (35 x 7.5 or 35 x 15mm

    per DIN EN5002).Termination Box Lug

    EnvironmentalOperating Temperature -10 C to +50 C

    2 http://www.morssmittrelais.com

    General technical specifications - PDR-Series

    1000

    1

    10

    100

    1001010.10.010.001

    0.01

    0.1

    O

    H

    M

    S

    AMPERE RATING

    CURRENT(AMPS)

    0.10 - 5.0

    5.1 - 20.0

    15%

    25%

    TOLERANCE(%)

    20.1 - 50.0 35%

  • 7/30/2019 Pdr Series

    3/9

    11 AGENCY APPROVALS 5

    1 UL-Recognized, CSA, TUV to EN60077 and NF F62-001

    3http://www.morssmittrelais.com

    3Current Rating

    6Circuit

    2Voltage/

    Poles

    PDR 244

    Frequency

    & Delay

    1Series

    B 6108

    Actuator

    Color

    5Equipment

    leakagetrip current

    7Actuator

    10Mounting

    9Terminal

    B 1 1B 1B

    2 SYSTEM VOLTAGE/POLES 1

    System Voltage PolesA 120VAC 1 One plus unswitched neutralB 120/240 VAC 1 TwoC 120/208 VAC 1, Two plus unswitched neutral

    120/240 VAC 1D 120/208 VAC 1, Two plus switched neutral

    120/240 VAC 1

    E 208/240 VAC 3 ThreeF 208/240 VAC 3 Three plus unswitched neutralG 208/240 VAC 3 Three plus switched neutralP 480Y VAC 3 ThreeQ 480Y VAC 3 Three plus unswitched neutralR 480Y VAC 3 Three plus switched neutral

    4 FREQUENCY & DELAY

    20 50/60Hz Instantaneous22 50/60Hz Short

    24 50/60Hz Medium26 50/60Hz Long

    6 CIRCUIT

    B Series Trip (Current)

    7 ACTUATOR

    A HandleB Handle with handleguard

    1 SERIES

    PDR

    5 EQUIPMENT LEAKAGE - TRIP CURRENT (milliamps) 2

    B 7C 10

    D 15E 30

    F 50G 100

    8 ACTUATOR COLOR & LEGEND

    Actuator Color Marking Marking Color Color: I-O ON-OFF DualWhite A B 1 BlackBlack C D 2 WhiteRed E F 3 White

    Ordering Scheme - PDR-Series

    3 CURRENT RATING (AMPERES)

    410 1.000512 1.250415 1.500517 1.750420 2.000522 2.250425 2.500527 2.750430 3.000

    435 3.500440 4.000

    445 4.500450 5.000455 5.500460 6.000465 6.500470 7.000475 7.500480 8.000485 8.500

    490 9.000495 9.500

    610 10.000710 10.500611 11.000711 11.500612 12.000712 12.500613 13.000614 14.000615 15.000

    616 16.000617 17.000

    717 17.500618 18.000619 19.000620 20.000622 22.000624 24.000625 25.000630 30.000635 35.000

    640 40.000650 50.000

    10 MOUNTING 3

    1 Threaded Insert 6-32 x 0.195 inches2 Threaded Insert ISO M3 x 6.5 mm

    9 TERMINAL

    1 Front Connected Box Lug with Pressure Plate

    Notes:1 Units with a switched or unswitched neutral connection are the same size as a unit with an

    additional breaker pole (e.g. a 2-pole unit with a switched or unswitched neutral is the samephysical size as a 3-pole unit.)Switched neutral poles contain the same overcurrent protection as the other poles.

    2 The leakage currents shown will cause the breaker to trip (must-trip current). The must-holdcurrent is 67% of the must-trip current.

    3 All breakers are front panel mountable using screw size shown. Breakers may also bemounted on either 35mm x 7.5mm or 35mm x 15mm symmetrical DIN rail.

    5 Preliminary test results showed that the breakers comply to the EN60077 and NF F62-001. Certificates for UL-Recognized and CSA are available on request. For the EN60077and NF F62-001 the certificates will be available in short notice

    11Agency

    approval

    1

    * Other values on request

  • 7/30/2019 Pdr Series

    4/9

    4 http://www.morssmittrelais.com

    Time Delay Values - PDR-Series

    NOTES:Delay Curves 22,24,26: Breakers to hold 100% and must trip at 125% of rated current and greater within the time limit shown in this curve.Delay Curves 20: Breakers to hold 100% and must trip at 150% of rated current and greater within the time limit shown in this curve.All Curves: Curve data shown represents breaker response at ambient temperature of 25C (77F) with no preloading. Breakers are mounted in standard wall-mount position.On 50 amp and less current ratings, the minimum inrush pulse tolerance handling capability is 12 times the rated current on standard delays and 25 times the rated current on high inrush delays. These val-ues are based on a 60 Hz 1/2 cycle, 8.33 ms pulse. High inrush delays should be specified for applications with high initial surge currents of short duration such as switching power supplies, highly capacitiveloads and transformer loads.

    AC

    1000 1100 1200

    10000

    1000

    100

    10

    1

    .1

    .01

    .001

    50/60 HzINSTANTANEOUS

    CURVE NO. 20

    150

    125

    100 200 300 400 500 600 700 800 900

    TRIPTIMEIN

    SECONDS

    PERCENT OF RATED CURRENT

    Instantaneous Short

    Medium Long

    800 900 1000 1100 1200

    10000

    1000

    100

    10

    1

    .1

    .01

    .001

    50/60 HzSHORT DELAYCURVE NO. 22

    TRIPTIMEIN

    SECONDS

    PERCENT OF RATED CURRENT150125

    100 200 300 400 500 600 700

    700 800 900 1000 1100 1200

    10000

    1000

    100

    10

    1

    .1

    .01

    .001

    50/60 HzMEDIUM DELAYCURVE NO. 24

    150

    125

    100 200 300 400 500 600

    PERCENT OF RATED CURRENT

    TRIPTIMEIN

    SECONDS

    700 800 900 1000 1100 1200

    10000

    1000

    100

    10

    1

    .1

    .01

    .001

    50/60 HzLONG DELAYCURVE NO. 26

    150

    125

    100 200 300 400 500 600

    PERCENT OF RATED CURRENT

    TRIPTIMEIN

    SECONDS

    DELAY 100% 125% 135% 150% 200% 400% 600% 800% 1000% 1200%

    20 No Trip May Trip --- .040 MAX .035 MAX .030 MAX .025 MAX .020 MAX .017 MAX .015 MAXTRIP

    22 No Trip .700 - 12.0 --- .350 - 4.00 .130 - 1.30 .027 - .220 .008 - .130 .004 - .090 .004 - .045 .004 - .040TIME

    24 No Trip 10.0 - 160 --- 6.00 - 60.0 2.20 - 20.0 .300 - 3.00 .050 - 1.30 .007 - .500 .005 - .060 .005 - .040(SECONDS)

    26 No Trip 50.0 - 700 --- 32.0 - 350 10.0 - 90.0 1.50 - 15.0 .500 - 7.00 .020 - 3.00 .006 - 2.00 .005 - 1.00

    PERCENT OF RATED CURRENT

  • 7/30/2019 Pdr Series

    5/9

    All dimensions in inches and [mm]

    5http://www.morssmittrelais.com

    Circuit & Terminal Diagrams - PDR-Series

    TEST

    P1(L1) LINE

    LINEP1(L1)

    TEST

    (N)

    LINEP1(L1) (N)

    LOAD

    LOAD

    TEST

    LOAD

    TRIPPED DUE TOEARTH LEAKAGE

    INDICATOR

    P3(L3)

    SENSOR

    CIRCUIT SCHEMATICS

    SOLID STATECIRCUITRY

    TRIPMECHANISM

    TRIPMECHANISM

    1-POLE CIRCUIT

    (N)

    SOLID STATECIRCUITRY

    P1(L)

    SENSOR

    TRIPPED DUE TOEARTH LEAKAGE

    INDICATOR

    SOLID STATE

    CIRCUITRY

    SOLID STATECIRCUITRY

    P3(L3)

    SENSOR

    P3(L3)

    TRIPPED DUE TOEARTH LEAKAGE

    INDICATOR

    LINE

    TRIPMECHANISM

    P2(L2)

    TRIPPED DUE TOEARTH LEAKAGE

    INDICATOR

    P1(N)

    P1(L1)P2(L2)

    P2(L)

    SOLID STATECIRCUITRY

    P1(L1)

    SENSOR

    SOLID STATE

    CIRCUITRY

    TRIPMECHANISM

    TRIPMECHANISM

    LOAD

    TEST

    LINE

    SENSOR

    TEST

    LOAD

    P2(L2)

    SOLID STATECIRCUITRY

    P1(L1)

    SENSOR

    TRIPMECHANISM

    TRIPMECHANISM

    TRIPPED DUE TOEARTH LEAKAGE

    INDICATOR SENSOR

    PDR D (WITH SWITCHED NEUTRAL)

    LINE

    (N)

    2-POLE CIRCUITSPDR B

    TEST

    LOAD

    PDR C (WITH UNSWITCHED NEUTRAL)

    LINE

    PDR A

    TEST

    (N)

    LOAD

    TRIPPED DUE TOEARTH LEAKAGE

    INDICATOR

    TRIPPED DUE TOEARTH LEAKAGE

    INDICATOR

    P2(L2)

    P2(L2)

    P2(L2)

    3-POLE CIRCUITS

    PDR G & PDR R (WITH SWITCHED NEUTRAL)

    PDR F & PDR Q (WITH UNSWITCHED NEUTRAL)

    PDR E & PDR P

    POLE2(L2)

    POLE3(L3)

    LINE

    (N)POLE1(L1)

    ONI

    LOAD

    OFF

    O

    POLE IDENTIFICATION SCHEME .920 [23.37]

    BOX TYPE WIRE CONNECTORSWITH PRESSURE PLATE

    1.500 [38.10] 4.500 [114.30]

  • 7/30/2019 Pdr Series

    6/9

    30

    60

    LINE

    (2 PLACES PER POLE)

    ONI

    2.250 [57.15]

    ONI

    LEAKAGE INDICATOR

    .375 [9.53]

    3.000 [76.20]

    ONI

    .550 [13.96]

    ONI

    4.500 [114.30]

    2.500 [63.50]

    PANEL CUT-OUT DETAIL

    2.260 [57.40]

    .650 [16.51]

    2.260 [57.40]

    .265 [6.73]

    TRIPPED DUE TO EARTH

    1.215 [30.86]

    PDR C & PDR D

    PDR A & PDR B

    PDR E &PDR P

    2.250 [57.15]

    1.125 [28.58]

    2.250 [57.15]

    .790 [20.10]

    LOAD

    PDR F, PDR G

    PDR Q & PDR R

    ASSEMBLY

    4.200 [106.68]

    TEST BUTTON

    6-32 [M3] THREAD x .195 [4.95] DEEP

    2.062 [52.37]

    .750 [19.05]

    .649 [16.48]

    SCREW DRIVER

    STANDARD 35mm SYMMETRICAL DIN RAIL

    1.405 [35.69]

    4.200 [106.68]

    OPTIONAL HANDLE GUARD

    REMOVAL

    (35 x 7.5 OR 35 x 15mm PER DIN EN50022).

    .150 [3.81]3.750 [95.25]

    2.062 [52.37]

    .156 DIA [3.96]

    1.510 [38.35]

    4 PLCS.

    3.500 [88.90]

    .644 [16.36]

    6 http://www.morssmittrelais.com

    Form & Fit Drawings - PDR-Series

    All dimensions in inches and [mm]

  • 7/30/2019 Pdr Series

    7/9

    7http://www.morssmittrelais.com

    Response Fax

    Please send more information for:

    Call for an appointment

    Please add me to the mailing list

    Please remove me from the mailing list

    Company: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Contact person: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Address: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    ZIP-code: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Place: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Telephone number: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fax number: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Email: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Relays (instantaneous relays, measuring and monitoring relays and electronic time delay relays)

    Circuit protection (hydraulic/magnetic circuit breakers, hydraulic/magnetic ground faultbreakers and hydraulic/magnetic remote operated breakers)

    High voltage and current protection relays (overcurrent, undercurrent, differential current,

    overvoltage, undervoltage, differential voltage and frequency measuring & monitoring relays)

    Electrical control solutions (Form, fit and function electrical control units for retrofit/refurbishmentapplications and new built applications)

    Panel indicators (analogue indicators for speed, voltage, current, power etc.)

    MORE INFORMATION?

    Fill in the details below and return this fax to:

    The Netherlands: +31 (0)30 289 88 16

    France: +31 (0)1 48 55 90 01

    USA: +1 (0)631 271 8898

  • 7/30/2019 Pdr Series

    8/9

    8

    France USA

    Your local distributor:

    For further information please contact:

    Proven Reliability

    The Netherlands

    ComDocSolutions-2004

    DS/GB PDR-Series 1.50 / 04-04

    MORS SMITT TECHNOLOGIES INC.

    50 North New York AvenueHuntington, NY, 11743USATel. +1 (631) 271-8858Fax +1 (631) [email protected]

    http://www.morssmittrelais.com

    MS RELAIS SAS

    Tour Rosny 2Avenue du Gnral de GaulleF - 93118 Rosny-sous-Bois CedexFranceTel. +33 (0)1 48 12 14 40Fax +33 (0)1 48 55 90 [email protected]

    http://www.morssmittrelais.com

    NIEAF-SMITT BV

    Vrieslantlaan 6NL - 3526 AA, UtrechtThe NetherlandsTel. +31 (0)30 288 13 11Fax +31 (0)30 289 88 [email protected]

    http://www.nieaf-smitt.nl/railway

  • 7/30/2019 Pdr Series

    9/9

    Aust ral ian Dist ri bu to r

    Relay Monitoring Systems Pty Ltd6 Anzed CourtMulgrave, Victoria, 3170, Australia

    Phone: +61 3 8544 1200Fax: +61 3 8544 1201Email: [email protected]: www.rmspl.com.au