CALCULO DE OCUPACION DE CONDUIT PROY. MONTAJE BOMBAS BOOSTER TSCZ ANEXO 1 CONDUIT DESDE TAB. POTENCIA HASTA TAB. ARRANCADORES GLP Y GN CONDUCTORES: INDUSCABOS 50 mm2 90G 1kV Enter Cable ODs and Qty Rigid Metal Conduit (RMS) Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area INDUSCABOS 50 mm2 0.52 0.212372 9 1.911345 1/2 0.632 0.3137 0.1255 0 3/4 0.836 0.5489 0.2196 0 1 1.063 0.8875 0.3550 0 1 1/4 1.394 1.5262 0.6105 0 1 1/2 1.624 2.0714 0.8286 0 2 2.083 3.4078 1.3631 0 2 1/2 2.489 4.8656 1.9463 0 3 3.090 7.4991 2.9996 0 3 1/2 3.570 10.0098 4.0039 0 4 4.050 12.8825 5.1530 Total 9 1.911345 5 5.073 20.2125 8.0850 6 6.093 29.1576 11.6631 NEC Chapter 9 Table 1 Number of Conductors Percentage 1 53.00% 2 31.00% over 2 40.00% NOTA 1.- SE UTILIZARA CONDUIT DE 2 1/2" DE DIAMETRO PARA EL CABLEADO DE POTENCIA DESDE EL TABLERO DE DISTRIBUCION HASTA LOS ARRANCADORES SUAVES NOTA 2.- SE UTILIZARA EL MISMO DIAMETRO DE CONDUIT PARA INSTALACION DE POTENCIA DESDE TABLEROS DE ARRANCADORES GLP Y GN HASTA LA CAMARA DE PASO

Ocupacion de Conduit

Embed Size (px)

Citation preview

Page 1: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE TAB. POTENCIA HASTA TAB. ARRANCADORES GLP Y GN

CONDUCTORES: INDUSCABOS 50 mm2 90G 1kV

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)INDUSCABOS 50 mm2 0.52 0.2123717 9 1.911345 1/2 0.632 0.3137 0.1255 n/a

0 3/4 0.836 0.5489 0.2196 n/a0 1 1.063 0.8875 0.3550 n/a0 1 1/4 1.394 1.5262 0.6105 n/a0 1 1/2 1.624 2.0714 0.8286 n/a0 2 2.083 3.4078 1.3631 n/a0 2 1/2 2.489 4.8656 1.9463 39.280 3 3.090 7.4991 2.9996 25.490 3 1/2 3.570 10.0098 4.0039 19.090 4 4.050 12.8825 5.1530 14.84

Total 9 1.911345 5 5.073 20.2125 8.0850 9.466 6.093 29.1576 11.6631 6.56

NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 2 1/2" DE DIAMETRO PARA EL CABLEADO DE POTENCIA DESDE EL TABLERO DE DISTRIBUCION HASTA LOS ARRANCADORES SUAVES

NOTA 2.- SE UTILIZARA EL MISMO DIAMETRO DE CONDUIT PARA INSTALACION DE POTENCIA DESDE TABLEROS DE ARRANCADORES GLP Y GN HASTA LA CAMARA DE PASO

Page 2: Ocupacion de Conduit
Page 3: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE TAB. ACTUADORES HASTA CAMARA DE PASO

CONDUCTORES: INDUSCABOS 50 mm2 90G 1kV

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)INDUSCABOS 3 x 2.5 mm2 0.38 0.1134115 1 0.1134115 1/2 0.632 0.3137 0.1255 n/aINDUSCABOS 3 x 2.5 mm2 0.38 0.1134115 1 0.1134115 3/4 0.836 0.5489 0.2196 n/aINDUSCABOS 3 x 2.5 mm2 0.38 0.1134115 1 0.1134115 1 1.063 0.8875 0.3550 n/aINDUSCABOS 3 x 2.5 mm2 0.38 0.1134115 1 0.1134115 1 1/4 1.394 1.5262 0.6105 29.72Cable Five 0 0 1 1/2 1.624 2.0714 0.8286 21.90Cable Six 0 0 2 2.083 3.4078 1.3631 13.31Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 9.32Cable Eight 0 0 3 3.090 7.4991 2.9996 6.05Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 4.53Cable Ten 0 0 4 4.050 12.8825 5.1530 3.52Total 4 0.453646 5 5.073 20.2125 8.0850 2.24

6 6.093 29.1576 11.6631 1.56NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 1 1/2" DE DIAMETRO PARA EL CABLEADO DE POTENCIA DESDE TABLERO DE DISTRIBUCION HASTA LA CAMARA DE PASO

Page 4: Ocupacion de Conduit
Page 5: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE TAB. ARRANCADORES GLP Y GN HASTA RTU (SEÑALES 24 VDC

CONDUCTORES: MARLEW AR5200 AWG 16

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)MARLEW 5200 0.24 0.0452389 8 0.3619115 1/2 0.632 0.3137 0.1255 n/aMARLEW 5200 0.24 0.0452389 8 0.3619115 3/4 0.836 0.5489 0.2196 n/aCable Three 0 0 1 1.063 0.8875 0.3550 n/aCable Four 0 0 1 1/4 1.394 1.5262 0.6105 n/aCable Five 0 0 1 1/2 1.624 2.0714 0.8286 34.94Cable Six 0 0 2 2.083 3.4078 1.3631 21.24Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 14.88Cable Eight 0 0 3 3.090 7.4991 2.9996 9.65Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 7.23Cable Ten 0 0 4 4.050 12.8825 5.1530 5.62Total 16 0.7238229 5 5.073 20.2125 8.0850 3.58

6 6.093 29.1576 11.6631 2.48NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 1 1/2" DE DIAMETRO PARA CABLEADO DE SEÑALES 24 VDC DESDE ARRANCADORES SUAVES HASTA TABLERO RTU

Page 6: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE TAB. RTU HASTA CAMARA DE PASO

CONDUCTORES: MARLEW AWG 16 Y BELDEN 1119A (RTD)

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)BELDEN 1119A (RTD) 0.3 0.0706858 8 0.5654867 1/2 0.632 0.3137 0.1255 n/aMARLEW 5200 0.24 0.0452389 10 0.4523893 3/4 0.836 0.5489 0.2196 n/aCable Three 0 0 1 1.063 0.8875 0.3550 n/aCable Four 0 0 1 1/4 1.394 1.5262 0.6105 n/aCable Five 0 0 1 1/2 1.624 2.0714 0.8286 n/aCable Six 0 0 2 2.083 3.4078 1.3631 29.87Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 20.92Cable Eight 0 0 3 3.090 7.4991 2.9996 13.57Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 10.17Cable Ten 0 0 4 4.050 12.8825 5.1530 7.90Total 18 1.017876 5 5.073 20.2125 8.0850 5.04

6 6.093 29.1576 11.6631 3.49NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 2 1/2" DE DIAMETRO PARA EL CABLEADO DE SEÑALES DESDE LA RTU HASTA LA CAMARA DE PASO

Page 7: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE TAB. RTU HASTA CAMARA DE PASO

CONDUCTORES: MARLEW AWG 16 Y BELDEN 1119A (RTD)

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)MARLEW 5200 0.24 0.0452389 10 0.4523893 1/2 0.632 0.3137 0.1255 n/aMARLEW 5200 0.24 0.0452389 10 0.4523893 3/4 0.836 0.5489 0.2196 n/aCable Three 0 0 1 1.063 0.8875 0.3550 n/aCable Four 0 0 1 1/4 1.394 1.5262 0.6105 n/aCable Five 0 0 1 1/2 1.624 2.0714 0.8286 n/aCable Six 0 0 2 2.083 3.4078 1.3631 26.55Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 18.60Cable Eight 0 0 3 3.090 7.4991 2.9996 12.07Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 9.04Cable Ten 0 0 4 4.050 12.8825 5.1530 7.02Total 20 0.9047787 5 5.073 20.2125 8.0850 4.48

6 6.093 29.1576 11.6631 3.10NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 2 1/2" DE DIAMETRO PARA EL CABLEADO DE SEÑALES DESDE LA RTU HASTA LA CAMARA DE PASO

Page 8: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE CAMARA DE PASO A JB-01

CONDUCTORES: INDUSCABOS 50 mm2 90G 1kV

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)INDUSCABOS 50 mm2 0.51 0.2042821 3 0.6128462 1/2 0.632 0.3137 0.1255 n/aCable Two 0 0 3/4 0.836 0.5489 0.2196 n/aCable Three 0 0 1 1.063 0.8875 0.3550 n/aCable Four 0 0 1 1/4 1.394 1.5262 0.6105 n/aCable Five 0 0 1 1/2 1.624 2.0714 0.8286 29.59Cable Six 0 0 2 2.083 3.4078 1.3631 17.98Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 12.60Cable Eight 0 0 3 3.090 7.4991 2.9996 8.17Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 6.12Cable Ten 0 0 4 4.050 12.8825 5.1530 4.76Total 3 0.6128462 5 5.073 20.2125 8.0850 3.03

6 6.093 29.1576 11.6631 2.10NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 1 1/2" DE DIAMETRO PARA EL CABLEADO DE POTENCIA POTENCIA DE BOMBA GLP-201 DESDE LA CAMARA DE PASO HASTA LA JUNCTION BOX JB-01

Page 9: Ocupacion de Conduit
Page 10: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE CAMARA DE PASO A JB-01

CONDUCTORES: INDUSCABOS 50 mm2 90G 1kV

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)Cables INDUSCABOS 0.51 0.2042821 3 0.6128462 1/2 0.632 0.3137 0.1255 n/aCable Two 0 0 3/4 0.836 0.5489 0.2196 n/aCable Three 0 0 1 1.063 0.8875 0.3550 n/aCable Four 0 0 1 1/4 1.394 1.5262 0.6105 n/aCable Five 0 0 1 1/2 1.624 2.0714 0.8286 29.59Cable Six 0 0 2 2.083 3.4078 1.3631 17.98Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 12.60Cable Eight 0 0 3 3.090 7.4991 2.9996 8.17Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 6.12Cable Ten 0 0 4 4.050 12.8825 5.1530 4.76Total 3 0.6128462 5 5.073 20.2125 8.0850 3.03

6 6.093 29.1576 11.6631 2.10NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 1 1/2" DE DIAMETRO PARA TRES DE SEIS CABLES DE POTENCIA DE BOMBA GN-200, SE UTILIZARA OTRO CONDUIT DE 1 1/2" PARA LOS TRES CABLES RESTANTES DESDE LA CAMARA DE PASO HASTA LA JUNCTION BOX JB-01

Page 11: Ocupacion de Conduit
Page 12: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE CAMARA DE PASO A JB-02

CONDUCTORES: INDUSCABOS AWG 16 (3 X 2.5mm2), 1 Kv

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)Cables INDUSCABOS 0.38 0.1134115 4 0.453646 1/2 0.632 0.3137 0.1255 n/aCable Two 0 0 3/4 0.836 0.5489 0.2196 n/aCable Three 0 0 1 1.063 0.8875 0.3550 n/aCable Four 0 0 1 1/4 1.394 1.5262 0.6105 29.72Cable Five 0 0 1 1/2 1.624 2.0714 0.8286 21.90Cable Six 0 0 2 2.083 3.4078 1.3631 13.31Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 9.32Cable Eight 0 0 3 3.090 7.4991 2.9996 6.05Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 4.53Cable Ten 0 0 4 4.050 12.8825 5.1530 3.52Total 4 0.453646 5 5.073 20.2125 8.0850 2.24

6 6.093 29.1576 11.6631 1.56NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 1 1/2" DE DIAMETRO PARA CABLEADO DE POTENCIA DE LOS CUATRO ACTUADORES DESDE LA CAMARA DE PASO HASTA LA JUNCTION BOX JB-02

Page 13: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE JB-01 HASTA BOMBA GLP

CONDUCTORES: INDUSCABOS AWG 16 (3 X 2.5mm2), 1 Kv

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)Cables INDUSCABOS 0.51 0.2042821 3 0.6128462 1/2 0.632 0.3137 0.1255 n/aCable Two 0 0 3/4 0.836 0.5489 0.2196 n/aCable Three 0 0 1 1.063 0.8875 0.3550 n/aCable Four 0 0 1 1/4 1.394 1.5262 0.6105 n/aCable Five 0 0 1 1/2 1.624 2.0714 0.8286 29.59Cable Six 0 0 2 2.083 3.4078 1.3631 17.98Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 12.60Cable Eight 0 0 3 3.090 7.4991 2.9996 8.17Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 6.12Cable Ten 0 0 4 4.050 12.8825 5.1530 4.76Total 3 0.6128462 5 5.073 20.2125 8.0850 3.03

6 6.093 29.1576 11.6631 2.10NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 1 1/2" DE DIAMETRO PARA CABLES DE POTENCIA DESDE LA JB-01 HASTA LA BOMBA GLP-201

Page 14: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE JB-01 HASTA BOMBA GN

CONDUCTORES: INDUSCABOS AWG 16 (3 X 2.5mm2), 1 Kv

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)Cables INDUSCABOS 0.51 0.2042821 6 1.2256924 1/2 0.632 0.3137 0.1255 n/aCable Two 0 0 3/4 0.836 0.5489 0.2196 n/aCable Three 0 0 1 1.063 0.8875 0.3550 n/aCable Four 0 0 1 1/4 1.394 1.5262 0.6105 n/aCable Five 0 0 1 1/2 1.624 2.0714 0.8286 n/aCable Six 0 0 2 2.083 3.4078 1.3631 35.97Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 25.19Cable Eight 0 0 3 3.090 7.4991 2.9996 16.34Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 12.24Cable Ten 0 0 4 4.050 12.8825 5.1530 9.51Total 6 1.2256924 5 5.073 20.2125 8.0850 6.06

6 6.093 29.1576 11.6631 4.20NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 2 1/2" DE DIAMETRO PARA CABLES DE POTENCIA DESDE JB-01 HASTA LA BOMBA GN-200 (2 CONDUCTORES POR FASE)

Page 15: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE JB-02 HASTA BOMBA GN

CONDUCTORES: INDUSCABOS AWG 16 (3 X 2.5mm2), 1 Kv

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)Cables Transmisores GLP 0.24 0.0452389 3 0.1357168 1/2 0.632 0.3137 0.1255 n/aCables Switches 0.24 0.0452389 1 0.0452389 3/4 0.836 0.5489 0.2196 n/aCables Actuadores GLP 0.24 0.0452389 8 0.3619115 1 1.063 0.8875 0.3550 n/aCables Botonera 0.24 0.0452389 3 0.1357168 1 1/4 1.394 1.5262 0.6105 n/aCable Five 0 0 1 1/2 1.624 2.0714 0.8286 32.76Cable Six 0 0 2 2.083 3.4078 1.3631 19.91Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 13.95Cable Eight 0 0 3 3.090 7.4991 2.9996 9.05Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 6.78Cable Ten 0 0 4 4.050 12.8825 5.1530 5.27Total 15 0.678584 5 5.073 20.2125 8.0850 3.36

6 6.093 29.1576 11.6631 2.33NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 1 1/2"DE DIAMETRO PARA CABLES DE INSTRUMENTACION Y CONTROL DE LA BOMBA DE GLP

Page 16: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE JB-01 HASTA BOMBA GN

CONDUCTORES: INDUSCABOS AWG 16 (3 X 2.5mm2), 1 Kv

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)Cables VE-GN 0.24 0.0452389 1 0.0452389 1/2 0.632 0.3137 0.1255 n/aCables RTD-GN 0.3 0.0706858 8 0.5654867 3/4 0.836 0.5489 0.2196 n/aCable Botonera 0 0 1 1.063 0.8875 0.3550 n/aCables Four 0 0 1 1/4 1.394 1.5262 0.6105 n/aCable Five 0 0 1 1/2 1.624 2.0714 0.8286 29.48Cable Six 0 0 2 2.083 3.4078 1.3631 17.92Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 12.55Cable Eight 0 0 3 3.090 7.4991 2.9996 8.14Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 6.10Cable Ten 0 0 4 4.050 12.8825 5.1530 4.74Total 9 0.6107256 5 5.073 20.2125 8.0850 3.02

6 6.093 29.1576 11.6631 2.09NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 1 1/2"DE DIAMETRO PARA CABLES DEL SWITCH DE VIBRACION Y DE LAS RTDs DE LA BOMBA DE GASOLINA

Page 17: Ocupacion de Conduit

CALCULO DE OCUPACION DE CONDUIT

PROY. MONTAJE BOMBAS BOOSTER TSCZ

ANEXO 1

CONDUIT DESDE JB-01 HASTA BOMBA GN

CONDUCTORES: INDUSCABOS AWG 16 (3 X 2.5mm2), 1 Kv

Enter Cable ODs and Qty Rigid Metal Conduit (RMS)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%)Cables Transmisores GLP 0.24 0.0452389 2 0.0904779 1/2 0.632 0.3137 0.1255 n/aCables Switches 0.24 0.0452389 1 0.0452389 3/4 0.836 0.5489 0.2196 n/aCables Actuadores GLP 0.24 0.0452389 8 0.3619115 1 1.063 0.8875 0.3550 n/aCables Botonera 0.24 0.0452389 3 0.1357168 1 1/4 1.394 1.5262 0.6105 n/aCable Five 0 0 1 1/2 1.624 2.0714 0.8286 30.58Cable Six 0 0 2 2.083 3.4078 1.3631 18.59Cable Seven 0 0 2 1/2 2.489 4.8656 1.9463 13.02Cable Eight 0 0 3 3.090 7.4991 2.9996 8.45Cable Nine 0 0 3 1/2 3.570 10.0098 4.0039 6.33Cable Ten 0 0 4 4.050 12.8825 5.1530 4.92Total 14 0.6333451 5 5.073 20.2125 8.0850 3.13

6 6.093 29.1576 11.6631 2.17NEC Chapter 9 Table 1Number of Conductors Percentage

1 53.00%2 31.00%

over 2 40.00%

NOTA 1.- SE UTILIZARA CONDUIT DE 1 1/2"DE DIAMETRO PARA CABLES DE INSTRUMENTACION Y CONTROL DE LA BOMBA DE GLP

Page 18: Ocupacion de Conduit

Conduit Fill Calculator provided by CommScopeEnter Cable ODs and Qty Electrical Metal Tubing (EMT) Flexible Metal Conduit (FMC)Cable Information OD (in) Area Quantity Total Area Trade Size ID (in) Area Permissable Area Fill (%) Trade Size ID (in) Area Permissable Area Fill (%)Cable One 0.38 0.1134115 1 0.1134115 1/2 0.622 0.3039 0.1215 n/a 3/8 0.384 0.1158 0.0463 n/aCable Two 0.38 0.1134115 1 0.1134115 3/4 0.824 0.5333 0.2133 n/a 1/2 0.635 0.3167 0.1267 n/aCable Three 0.38 0.1134115 1 0.1134115 1 1.049 0.8643 0.3457 n/a 3/4 0.824 0.5333 0.2133 n/aCable Four 0.38 0.1134115 1 0.1134115 1 1/4 1.380 1.4957 0.5983 30.33 1 1.020 0.8171 0.3269 n/aCable Five 0 0 1 1/2 1.610 2.0358 0.8143 22.28 1 1/4 1.275 1.2768 0.5107 35.53Cable Six 0 0 2 2.067 3.3556 1.3422 13.52 1 1/2 1.538 1.8578 0.7431 24.42Cable Seven 0 0 2 1/2 2.469 4.7878 1.9151 9.48 2 2.040 3.2685 1.3074 13.88Cable Eight 0 0 3 3.356 8.8457 3.5383 5.13 2 1/2 2.500 4.9087 1.9635 9.24Cable Nine 0 0 3 1/2 3.834 11.5450 4.6180 3.93 3 3.000 7.0686 2.8274 6.42Cable Ten 0 0 4 4.334 14.7526 5.9010 3.08 3 1/2 3.500 9.6211 3.8485 4.72Total 4 0.453646 4 4.000 12.5664 5.0265 3.61

NEC Chapter 9 Table 1 Intermediate Metal Conduit (IMC) Electrical Nonmetallic Tubing (ENT)

Number of Conductors Percentage Trade Size ID (in) Area Permissable Area Fill (%) Trade Size ID (in) Area Permissable Area Fill (%)

1 53.00% 1/2 0.660 0.3421 0.1368 n/a 1/2 0.560 0.2463 0.0985 n/a2 31.00% 3/4 0.864 0.5863 0.2345 n/a 3/4 0.760 0.4536 0.1815 n/a

over 2 40.00% 1 1.105 0.9590 0.3836 n/a 1 1.000 0.7854 0.3142 n/a1 1/4 1.448 1.6467 0.6587 27.55 1 1/4 1.340 1.4103 0.5641 32.17

Rigid PVC Conduit (RNC) Sch 40 & HDPE 1 1/2 1.683 2.2246 0.8899 20.39 1 1/2 1.570 1.9359 0.7744 23.43Trade Size ID (in) Area Permissable Area Fill (%) 2 2.150 3.6305 1.4522 12.50 2 2.020 3.2047 1.2819 14.16

1/2 0.602 0.2846 0.1139 n/a 2 1/2 2.557 5.1351 2.0541 8.83 3/4 0.804 0.5077 0.2031 n/a 3 3.176 7.9223 3.1689 5.73 Liquidtight Flexible Nonmetallic (LFNC-B)

1 1.029 0.8316 0.3326 n/a 3 1/2 3.671 10.5842 4.2337 4.29 Trade Size ID (in) Area Permissable Area Fill (%)1 1/4 1.360 1.4527 0.5811 31.23 4 4.166 13.6310 5.4524 3.33 3/8 0.494 0.1917 0.0767 n/a1 1/2 1.590 1.9856 0.7942 22.85 1/2 0.632 0.3137 0.1255 n/a2 2.047 3.2910 1.3164 13.78 Rigid Metal Conduit (RMS) 3/4 0.830 0.5411 0.2164 n/a

2 1/2 2.445 4.6951 1.8781 9.66 Trade Size ID (in) Area Permissable Area Fill (%) 1 1.054 0.8725 0.3490 n/a3 3.042 7.2679 2.9072 6.24 1/2 0.632 0.3137 0.1255 n/a 1 1/4 1.395 1.5284 0.6114 29.68

3 1/2 3.521 9.7369 3.8948 4.66 3/4 0.836 0.5489 0.2196 n/a 1 1/2 1.588 1.9806 0.7922 22.904 3.998 12.5538 5.0215 3.61 1 1.063 0.8875 0.3550 n/a 2 2.033 3.2461 1.2984 13.985 5.016 19.7608 7.9043 2.30 1 1/4 1.394 1.5262 0.6105 29.726 6.031 28.5673 11.4269 1.59 1 1/2 1.624 2.0714 0.8286 21.90 Liquidtight Flexible Nonmetallic (LFNC-A)

2 2.083 3.4078 1.3631 13.31 Trade Size ID (in) Area Permissable Area Fill (%)Type A Rigid PVC Conduit (RNC) 2 1/2 2.489 4.8656 1.9463 9.32 3/8 0.495 0.1924 0.0770 n/a

Trade Size ID (in) Area Permissable Area Fill (%) 3 3.090 7.4991 2.9996 6.05 1/2 0.630 0.3117 0.1247 n/a 1/2 0.700 0.3848 0.1539 n/a 3 1/2 3.570 10.0098 4.0039 4.53 3/4 0.825 0.5346 0.2138 n/a 3/4 0.910 0.6504 0.2602 n/a 4 4.050 12.8825 5.1530 3.52 1 1.043 0.8544 0.3418 n/a1 1.175 1.0843 0.4337 n/a 5 5.073 20.2125 8.0850 2.24 1 1/4 1.383 1.5022 0.6009 30.20

1 1/4 1.500 1.7671 0.7069 25.67 6 6.093 29.1576 11.6631 1.56 1 1/2 1.603 2.0182 0.8073 22.481 1/2 1.720 2.3235 0.9294 19.52 2 2.063 3.3426 1.3371 13.572 2.155 3.6474 1.4590 12.44 Rigid PVC Conduit (RNC) Sch 80

2 1/2 2.635 5.4532 2.1813 8.32 Trade Size ID (in) Area Permissable Area Fill (%) Liquidtight Flexible Metal (LFMC)3 3.230 8.1940 3.2776 5.54 1/2 0.526 0.2173 0.0869 n/a Trade Size ID (in) Area Permissable Area Fill (%)

3 1/2 3.690 10.6941 4.2776 4.24 3/4 0.722 0.4094 0.1638 n/a 3/8 0.494 0.1917 0.0767 n/a4 4.180 13.7228 5.4891 3.31 1 0.936 0.6881 0.2752 n/a 1/2 0.632 0.3137 0.1255 n/a

1 1/4 1.255 1.2370 0.4948 36.67 3/4 0.830 0.5411 0.2164 n/aType EB PVC Conduit (RNC) 1 1/2 1.476 1.7110 0.6844 26.51 1 1.054 0.8725 0.3490 n/a

Trade Size ID (in) Area Permissable Area Fill (%) 2 1.913 2.8742 1.1497 15.78 1 1/4 1.395 1.5284 0.6114 29.682 2.221 3.8742 1.5497 11.71 2 1/2 2.290 4.1187 1.6475 11.01 1 1/2 1.588 1.9806 0.7922 22.903 3.330 8.7092 3.4837 5.21 3 2.864 6.4422 2.5769 7.04 2 2.033 3.2461 1.2984 13.98

Page 19: Ocupacion de Conduit

3 1/2 3.804 11.3650 4.5460 3.99 3 1/2 3.326 8.6883 3.4753 5.22 2 1/2 2.493 4.8813 1.9525 9.294 4.289 14.4478 5.7791 3.14 4 3.786 11.2577 4.5031 4.03 3 3.085 7.4748 2.9899 6.075 5.316 22.1952 8.8781 2.04 5 4.768 17.8551 7.1420 2.54 3 1/2 3.520 9.7314 3.8926 4.666 6.336 31.5297 12.6119 1.44 6 5.709 25.5982 10.2393 1.77 4 4.020 12.6923 5.0769 3.57