RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 1

Remote Control MonitorOPERATION AND MAINTENANCE

Technical changes reserved without notice

Page 2: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 2

CONTENTS PAGE CONTENTS PAGE1. General description 3

1.1 Function and Handling 31.2 Liability Warning 31.3 Warranty 31.4 Installation 3

1.4.1 Safety 3

2. Hazard warning 4

3. Adjustments and Calibration 5

3.1 Monitor Type 53.2 Mechanical Movement Limitation 53.3 POS - Positioning System 6

3.3.1 Electrical Installation 6

3.3.2 Positioning Settings 6

3.4 LS - Limit Switching 7

3.4.1 Electrical Installation 7

3.4.2 Setting Limits Rotation 7

3.4.3 Setting Limits Elevation 7

3.5 Nozzle Settings 8

3.5.1 Standard Nozzle 8

3.5.2 ATEX Nozzle Settings 8

3.5.3 Flow Setting 9

3.7 Functional Test 10

3.7.1 Test for RCM LS and EX 10

3.7.1 Test for RCM POS 10

4. Operation instruction 11

4.1 Remote Operation 114.2 After use 114.3 Automated Operation 11

5. Upkeep 12

5.1 Maintenance 12

5.1.1 Every month 12

5.1.2 Every 2 months 12

5.2 Service 125.3 Spare parts 13

6. General Troubleshooting 14

INDEX

Page 3: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 3

1. General descriptionThe Incendium RCM is an efficient, compact and reliable Remotely Operated Monitor. The capacity of the monitor can be adjusted to excel in performance for different water pressures that are available. The RCM can be equipped with a wide range of various equipment which allows for customer specific solutions.

1.1 Function and HandlingThe RCM is used to discharge extinguishing agent in the form of water or foam. The monitor is operated remotely by either a control panel, a radio control unit or as a part of an automated system and can discharge the agent in either jet or fog-mode, covering large areas. When the monitor is activated, the water is discharged under high pressure and can pose several risks to the surrounding area and personnel. The monitors design pressure should not be exceeded in order to prevent damage and accidents.

Please read through this entire manual before operating the monitor. Incendium is not responsible for any accidents that occur if not following the instructions in this document.

1.2 Liability WarningThe RCM must be operated and maintained in compliance with this document as well as with applicable standards, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the proper operation or integrity of this device.

The owner is responsible for maintaining his fire protection unit or system and devices in proper operating conditions. The manufacturer or reseller should be contacted relative to any questions.

This manual must be read and understood by all personnel involved in operation, calibration and maintenance of this prod-uct and shall be kept in an accessible place for review. Take note that the appearance of the monitor in this manual can differ from the delivered product. The functions are however the same and thus, this manual must be followed with every step.

The unit should not under any circumstance be operated outside the angle or pressure range as indicated in this manual. Operation of this device without understanding this manual can be dangerous.

1.3 WarrantySeller warrants for a period of one year from date of shipment (warranty period) that products furnished hereunder will be free from defects in material and workmanship.

This warranty is invalid if the device is, or has been: • Misused or neglected• If there have been accidents to the equipment • Altered in any way• Instructions in this manual has not been followed

1.4 InstallationFor standard installation instructions, please see documents (order specific instructions can also be provided): Limit switch type, document designation: II-0004-RCM-LS-ENPositioning type, document designation: II-0005-RCM-POS-EN

1.4.1 SafetyThe following points must be respected during installation:• The installation must be carried out by qualified personnel. The directions given in the installation instruction must be

followed.• Make sure that the RCM is safely secured when installing and running the system. • Use only lifting gear and equipment that are well suited for the purpose.• Do not lift the monitor by hand.• Before start up of testing make sure there is no personal in the affected area.

Page 4: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 4

2.1 Remove handle after use. If still present when motor active these may cause harm.!

2.2 Risk of injury when operating up/down. Stay clear of monitor when in use.

2.6 Risk of injury when operating up/down. Stay clear of monitor when in use.

2.3 Risk of pinching when using up/down or fog/jet. Stay clear of monitor when in use.

2.5 Risk of pinching when operating left/right. Stay clear of monitor when in use.

!2.7 Do not point monitor at personnel or sensitive equipment when in use. Monitor should always be parked towards a safe location when not in use.

2. Hazard warningOperating the monitor can pose several risks to personnel and equipment. Be advised the risks in the below section before using the RCM.• The manual override handle (2.1) is only to be used when the monitors power source is disconnected. Remove after use

to prevent risk of injury. • The RCM is fitted with gear covers (2.2, 2.6) to limit pinching and other injuries. These must only be removed during

authorized maintenance and thereafter replaced.

Incendium does not take responsibility for any injuries that occur by not using the RCM in accordance with this chapters stated recommendations.

2.4 Connection box. Do not open when power is connected.

Page 5: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 5

3. Adjustments and CalibrationAfter installation has been completed, all chapters relevant for your monitor must be read and understood to ensure correct functionality of the RCM. When adjustments has been completed, set the monitors in a safe parked position to ensure that activation does not factor a risk.

3.1 Monitor TypeThe RCM is made for both SAFE area and with ATEX equipment and comes in several different combinations. For the ATEX monitors the operation and maintenance are the same with the exception of the nozzle (EON) where the settings differ (see “3.5.2 ATEX Nozzle Settings” on page 8). The type of monitor can be identified by the combination of letters that follows the size designation. The following combinations can be read from the full model number:

Example: RCM-150 EL DIN EX POS EON-140

1. RCM-xxx EL- Size of monitor2. DIN/ANSI - Type of connection 3. EX - Only present if monitor has ATEX equipment4. POS - If monitor has positioning system - Check “3.3 POS - Positioning System” on page 64. LS - If monitor has limit switching - Check “3.4 LS - Limit Switching” on page 75. EON-xxx - Size of nozzle - Check “3.5 Nozzle Settings” on page 8

3.2 Mechanical Movement LimitationThe RCM is delivered without any mechanical stops to allow for maximum movement and ease of installation. If however a mechanical stop of rotation is needed, one of the connecting bolts can be flipped as shown below.

HEIGHT OF MECHANICAL STOP SCREW, ROTATION

ModelH [mm]

Connection Min Max

RCM-80 DIN 30 40 DN80 PN16

RCM-80 ANSI 45 55 ANSI 3” 150 lbs

RCM-100 DIN 30 40 DN100 PN16

RCM-100 ANSI 50 60 ANSI 4” 150 lbs

RCM-150 DIN 35 45 DN150 PN16

RCM-150 ANSI 65 75 ANSI 6” 150 lbs

H

All sizes of the RCM can elevate +70° -90°. RCM with LS can rotate ±172° (345°) and RCM with POS can rotate more than ±180° (360°+) depending on cable length.

70°

90°

LS type: ±172,5°POS type: over ±180°

LS/POS

LS/POS

Page 6: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 6

3.3 POS - Positioning SystemThe RCM EL with POS uses pulse counting as a method for giving precise angular measurement of rotation and elevation of the moni-tor. The RCM POS is used where exact positions are needed such as in automated systems.

The POS version of the RCM is installed according to installation in-struction with document number: II-0005-RCM-POS-EN

3.3.1 Electrical InstallationBefore switching on power, make sure that each monitor has been connected in accordance with the orders associated External Wiring Diagram and that the PLC has the correct program installed to be able to read the position given by the monitor. This should be carried out by authorized staff only.

3.3.2 Positioning SettingsZero position as well as maximum positions are set via software in the PLC panel provided by Incendium. The program uses a reset position as origin of movement and it is crucial that this origin is set correctly. Depending on the situation in which the RCM POS is used, the monitor should point toward the centre of the protected area in regards to rotation and at 0° elevation/horizontal as shown to the right.

Depending on the size of the monitor, the pulses given for movement differs in terms of degrees moved. Using a system from Incendium, zero position is always 1000 pulses elevation and 1000 pulses rotation.

Use the table below when setting position limits. For degree specific setting, divide wanted angle position with [°/pulse] value for the given monitor and round down. Example: RCM-80 elevation up +50°: 50°/ 0,74°= 67 pulses

POSITION LIMITING PULSES/DEGREES

Model Rotation[°/pulse]

Max rotation right +180°[pulses / PLC setting]

Max rotation left -180°[pulses / PLC setting]

Elevation[°/pulse]

Max. elevation up +70°[pulses / PLC setting]

Max. elevation down -90°[pulses / PLC setting]

RCM-80 0,98° 184 / 1184 184 / 816 0,74° 94 / 1094 94 / 906

RCM-100 0,76° 236 / 1236 236 / 764 0,62° 113 / 1113 113 / 887

RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155 / 845

Take note that manually overriding rotation or elevation also bypasses the positioning system. This means that a reset on zero position must be made after overriding.

Page 7: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 7

3.4 LS - Limit SwitchingThe RCM EL with LS uses limit switches to set maximum elevation and rotation positions. The RCM LS is used mainly in manual systems where only outer limits are needed to protect surrounding structure or to limit the allowed extinguishing area of the monitor.

The LS version of RCM is installed according to installation instruction with document number: II-0004-RCM-LS-EN

3.4.1 Electrical InstallationBefore switching on power, make sure that each monitor has been connected in accordance with the orders associated External Wiring Diagram. This should be carried out by authorized staff only. If installed incorrectly, the monitor or surrounding structure could take damage.

3.4.2 Setting Limits RotationIf installed correctly according to installation instructions, the RCM LS monitor should point toward the centre of the protected area in regards to rotation. Limiting rotation is done by moving two hexagon domed nuts to the relative position where right and left motion is desired to be stopped. As shown to the right, rotation left is stopped by the closest nut (2) to the right of the dual limit switches(1). This is because the switches are the ones that are moving and not the stops themselves. To limit the rotation, move the two hexagon domed nuts to the desired posi-tions. The manual override handle can be used to aid in this proce-dure (replace after use according to 2.1).

In addition to moving the domed nuts, the entire stop plate can be rotated by slightly loosening the screw (3) and nut (4) fixation around the monitor base. Re-tighten, being careful not to bend plate, after adjusting.

3.4.3 Setting Limits ElevationThe RCM LS is normally delivered with elevation limiting nuts (5,6) set to absolute maximum (+70°, -90°). If further limiting is desired, these nuts can be loosened and tightened in the desired position. In the example below, the nut for limiting up-wards motion is stopped at +50°. The upper nut (5) is loosened slightly and moved down to the dual limit switches (7) until it audibly clicks. The nut can now be tightened resulting in a maximum upward elevation of 50°.

65

5

7

1 2

3 4

Page 8: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 8

3.5 Nozzle SettingsThe RCM consists of the monitor base (RCM) and the nozzle (EON). Each size of RCM has two possible nozzles that can be used depending on the pressure and flow required.

3.5.1 Standard NozzleAs standard the nozzle comes with a linear actuator 24VDC which is used for maneuvering between fog (wide water spray) and jet (directed water jet). The linear actuator is equipped with a potentiometer which allows for precise setting of the water stream. It is also equipped with internal switches that provides automatic stopping function at maximum fog and maximum jet.

3.5.2 ATEX Nozzle Settings The ATEX nozzle (EON) consists of the standard type nozzle and a mechanical linear actuator (1) in combination with a three-phase motor (2) and limit switching (3) for fog-/jet operation (instead of a 24VDC linear actuator). The flow/pressure setting is however the same as for the standard nozzles.

Calibration of fog-/jet setting is done at factory but if changes needs to be made the following settings can be made. Adjust-ing the hexagon domed nut (4) up and down changes the trigger depth of both limit switches (3). Upwards adjusted domed nut (4) equals earlier triggering which means that stop for fog happens earlier (movement of outer pipe backward is stopped earlier) as well as for jet (movement of outer pipe forward is stopped earlier). Opposite movement of domed cap achieves the a later triggering by the same principle. The switches (3) can also be adjusted independently by loosening the bolt connection (5) holding each switch in place. The trigger depth can then be adjusted by moving the limit switch (3) down for earlier triggering and up for later triggering. The bolt connection (5) is then tightened carefully at desired position.

2

1

5

3

4

Page 9: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 9

3.5.3 Flow SettingNormally, the EON is calibrated in factory according to the pressure and flow specified at the time of purchase. Changing this calibration can however be required on site when the pressure or flow differs from what has previously been stated. The capacity of the nozzle is adjusted by turning the nozzle disc, increasing or decreasing the opening. For specific pressure and flow per turns of disc information, see the specific size of nozzle section.To adjust the nozzle opening, unscrew the counter-locking nut (2) holding the disc (1) in place. Turn disc clockwise until contact with nozzle outlet and make a mark (3) to be able to easily count rotations. Turn disc (1) counter-clockwise until, as specified for the nozzle in question, enough rotations has been achieved. Tighten counter-locking nut (2) while holding the disc (1).

1 1 1

2

2

3

If the flow is adequate, but the throw length is lacking, the pressure needs to be increased. This can be done by turning the disc inwards and testing intermittently until good result has been achieved.If the throw length is good, but the flow is lacking, the flow needs to be increased. This can be done by turning the disc out-wards and testing intermittently until good result has been achieved. If any problems still persists, contact Incendium for assistance.

Page 10: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 10

3.7 Functional TestPay attention to potential hazards according to “2. Hazard warning” on page 4 before proceeding.All monitors should be tested for correct functionality via the control panel and the hand-held radio control (if supplied). When performing these tests, make sure that the water connection is closed and that personnel are aware of the tests taking place. When oper-ating from the control panel, at least one person should survey that the monitor moves in accordance to signals sent.

As with all three-phase motors, phase sequence can differ from site to site. All monitors should be checked for movement in the desired direction. If the monitor behaves differ-ently than expected, flip the sequence in the connection box until desired result has been achieved.

3.7.1 Test for RCM LS and EXWhen a monitor has any fixed limits, such as with RCM LS or when monitor has an ATEX Nozzle with stops for jet and fog, functionality can be tested easily. After the monitor has been connected according to the external wiring diagram, the moni-tors need to be tested for correct function. Correct rotation and elevation stopping of the monitor with LS can be tested by triggering the switch in question for each movement. Use a screwdriver or similar tool when triggering the switches to avoid pinching hazard. If movement does not stop when the correct trigger is pushed the connection is for some reason faulty and must be checked according to the external wiring diagram.

Rotation LS: When moving the monitor to the left, trigger the right switch (seen from behind the monitor) by pressing the wheel arm until it audibly clicks. Test the reverse situation as well.

Elevation LS:When moving the monitor up, trigger the upper limit switch by pressing the wheel arm until it audibly clicks. Test the reverse situation as well.

Nozzle EX:When moving the nozzle from fog to jet position, press the foremost switch until it audibly clicks. Test the reverse situation as well.

3.7.2 Test for RCM POSIf the RCM in question has POS, it also comes with a PLC panel to which there are separate instructions that must be read. The POS function is not direction sensitive and must therefore be checked for correct movement after installation. If the monitor does not move according to input, the connection is for some reason faulty and must be checked according to the external wiring diagram.

Check that the zero position is horizontal for elevation and that the monitor is pointing towards the center of protected area (zero position 1000:1000). Before testing maximum limits, first check that the pulse settings in the control panel corresponds with the table in chapter “3.3.2 Positioning Settings” on page 6. Make sure that max limits for elevation does not exceed the values given in this table. Rotation values can be set above the maximum limits of the table but only with supervision of the monitors movements (first time setting) to make sure that cable hose or other equipment is not damaged.

Take note that manually overriding rotation or elevation does also bypasses the positioning system. This means that a reset on zero position must be made after overriding.

In some cases the RCM POS also has EX functionality. If so, check the previous chapter for setting the EX nozzle.

For all other questions, please contact Incendium.

Make sure that the cable on the back of the monitor is in the shown position to ensure no harm will come to it during operation.

Page 11: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 11

4. Operation instruction

4.1 Remote Operation

1. Select which monitor to use through selection turn switch or push buttons.

2. Point the monitor towards the area of application using the joystick (1) for the selected monitor.

3. Open firewater valve for the selected monitor.

4. Adjust fog/jet ratio for the situation using the turn switch (2).

5. Close the firewater valve when done.

1 1

2

4.2 After useIf the monitor has been used with foam it needs to be flushed to avoid corrosion. If not skip points 1-4.

1. Point the monitor towards a safe flush location.

2. Before opening the firewater valve, make sure that the foam mixing equipment is closed / shut down.

3. Open the firewater valve and flush the monitor.

4. Close the firewater valve after flush has been completed.

5. Point the monitor downwards to drain the water in the nozzle and prevent freezing damage.

6. After draining has been completed, move the monitor to the correct parked position including fog/jet setting

4.3 Automated OperationAutomated systems from Incendium has separate instructions for each order. Please see order specific documentation.

WARNING-Do not direct the water jet towards people or sensitive equipment

Page 12: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 12

5. Upkeep

5.1 MaintenanceThe RCM as with any other monitor needs maintenance on a monthly to annual basis depending on function. Incendium has a complete range of spare parts for the monitor of which the most used are listed in chapter “5.3 Spare parts” on page 13. Always use Incendium products to ensure correct function of the monitor.To make sure that the monitor is in proper condition for its entire life-span, follow the steps below.

5.1.1 Every month• Test monitor without water, vertical and horizontal movement within the needed area/range. o Verify Up/Down movement o Verify Left/Right movement o Verify Fog/Jet movement o Verify zero position for RCM with POS• Check that elevation gear is free from damage or dirt. If the gear appears dry, apply worm gear grease (5.3 item 19).• Check for paint damage on the monitor. Restore damage by reapplying paint.

5.1.2 Every 2 months• Test complete function of monitor with water according to 4.1. Reset according to 4.2. • Check for any cable damage.• Check for debris in the nozzle when set to fog-mode. If debris is present, remove nozzle disc after documenting current

setting and flush according to chapter 4.2. Replace the nozzle disc at the same setting as before.

5.2 ServiceService needed for the RCM should be minimal if maintenance in chapter 5.1 is followed rigorously. In case of equipment malfunction the troubleshooting guide should be followed in chapter 6.

If problems persist after these steps has been taken or if any spare parts are needed, please contact Incendium for counsel or orders.

WARNING-Do not perform maintenance on the monitor when it is connected to power source.

Page 13: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 13

5.3 Spare partsSpare parts shown here are the ones likely to be damaged or in need of changing if accidents or other unforeseen events where to affect the monitor. Spare parts shown below are only the general setup of the spare parts that can be needed for an order. Motors and other material sensitive parts are order and size specific. Please see the orders spare parts list for further details.

Single spare parts can also be obtained from kits if needed.

Always contact Incendium directly if any these or other parts are needed.

1 2 3 4

5 6 7 89

10 11 12

1

5

6

27

48

9

10

11

VisibleNot Visible

GENERAL SPARE PARTS LIST

No Description Order / Size (Specific)

1 Motor and Gear, Elevation Yes / No

2 Motor and Gear, Rotation Yes / No

3 Linear Actuator (ATEX) Yes / No

4 Linear Actuator (Standard) Yes / No

5 Elevation Helical Worm Gear No / Yes

6 Elevation/Rotation Gear Screw No / No

7 Manual Override Handle No / No

8 O-ring Kit Nozzle No / Yes

9 O-ring Kit Monitor No / Yes

10 POS Full Spare Parts Kit No / No

11 LS Full Spare Parts Kit No / Yes

12 Nozzle EX Switches Spare Parts Kit No / No

Page 14: OPERATION AND MAINTENANCE - incendiumfire.comincendiumfire.com/.../Operation-and-Maintenance-RCM-OM-0003-RCM-EN.pdf · RCM-150 0,52° 344 / 1344 344 / 656 0,45° 155 / 1155 155

RCMOPERATION AND MAINTENANCE

OM-0003-RCM-EN

Revision: 18E23

Consilium Incendium AB Telephone: +46 303 44 00 30 E-mail: [email protected] www.incendiumfire.com 14

6. General Troubleshooting• Monitor does not move properly when given signals: o Check to see if monitor is in the expected starting position. o Check trigger and limit switches for damage. o Check for debris in gear and remove if present. Power must be disconnected during this operation. o Check if gears for rotation or elevation contain enough grease. o Check if monitor, motors or gears has damage. o Check emergency motor break switches and reset if triggered.• The monitor is leaking: o If leakage is coming from the flange of the monitor, check if all bolts have been properly tightened. o If leakage occurs from joints in the monitor the o-rings might need to be switched out. Contact Incendium. o If leakage occurs from joints between monitor and nozzle the two nuts on the groove coupling can be tightened.• The monitor produces an uneven jet or fog: o Check for debris inside nozzle. If debris is present, unscrew the nozzle disc and flush the monitor according to chapter 4.2. Then put back the nozzle disc at the same amount of turns as before. • The jet from the monitor is shorter than expected or weak: o Check that the pressure provided to the monitor is correct. o Adjust the nozzle disc according to chapter “3.5 Nozzle Settings” on page 8.• The nozzle does not maneuver as expected:

o Maneuver the nozzle from fog to jet several times. o Check for debris inside nozzle. If debris is present, unscrew the nozzle disc and flush the monitor according to chapter 4.2. Then put back the nozzle disc at the same amount of turns as before. o If the nozzle is of ATEX type, check for any problems with the mechanical actuator. If it has locked up and the plastic plug on the bottom has dropped out, the connection of motors or limit switches might be faulty and must be inspected. The actuator can unlocked by unscrewing the front screw and rotating the push piston counter-clock wise. The plastic plug on the bottom of the actuator can then be pushed back again and the screw fixing the push piston can be reinserted.

Contact Incendium if any problems persist.